beautypg.com

KEPCO BHK-MG 200W (Full Rack) Series User Manual

Page 20

background image

1-4

BHK-MG (OPR) 022014

OUTPUT CHARACTERISTICS (CONTINUED)

Withstand voltage

(All models) 1350V a-c/1 min

Between shorted inputs and chassis

BHK 300-0.6MG 1950V d-c/1 min

Between shorted outputs and chassis.

BHK 500-0.4MG 2250V d-c/1 min

BHK 1000-0.2MG

2800V d-c/1 min

BHK 2000-0.1MG

Chassis connection to ground
resistance

100 mohms max.

Between ground input connection and
chassis @ 30A

Leakage Current

25

µ

A rms /100 uA p-p, for 115V a-c input voltage

(chassis to EARTH-GND)

Enable/Disable Output Power

Local Front panel Keypad

Enables/disables digital programming sig-
nals only. Shutdown line is for disable only
- removing the signal does not reenable
the output (See PAR. 3.2.7.3).

Remote - IEEE 488 (GPIB) port

- RS 232 port
- Trigger port (shutdown
line)

Output Display

Output voltage is displayed with two decimals for BHK 300-0.6MG and
BHK 500-0.4MG and one decimal for BHK 1000-0.2MG and BHK
2000-0.1MG.Output current for all models is displayed with two deci-
mals when current range is set to High, and three decimals when cur-
rent range is set to Low.

Protection

Overtemperature:

See PAR. 1.4.10a

Overvoltage/Overcurrent: 0 to 1.1 x EOmax

0 to 1.1 x IOmax (except

BHK 300-0.6MG)
0 to 1.08 x IOmax (BHK

300-0.6MG only)

See PAR. 1.4.4

Uneven voltage/current

in pass element:

See PAR. 1.4.10c

Fan failure:

See PAR. 1.4.10d

AC line failure:

See PAR. 1.4.10e

Interruption between sens-

ing and power terminals:

See PAR. 1.4.10f

Overload of main or

auxiliary power transformer:

See PAR. 1.4.10g

Internal Output Capacitor
(Default state = internal output
capacitor connected.)

BHK 300-0.6MG 20

µ

F ±6%

All internal output capacitors are

non-polarized type.

BHK 500-0.4MG 10

µ

F ±6%

BHK 1000-0.2MG 4

µ

F±10%

BHK 2000-0.1MG 2

µ

F±10%

Reference Voltages for analog
programming:

+10 ±-0.2V d-c
–10 ±-0.2V d-c

max.10 mA d-c

Status port

Type Output transistor (open collector) from an optocoupler

Output Ratings Ic = 8mA d-c, Vceo = 40V d-c, Pd = 150mW@25° C

Logic Saturated transistor when AC line is present

Series Connection

Automatic or Master-
Slave Operation, limited
by the d-c isolation limit
voltage

For slave unit, use analog programming
only.

Parallel Connection

Automatic or Master-
Slave Operation

For slave unit, use analog programming
only.

TABLE 1-2. BHK-MG 200W SPECIFICATIONS (Continued)

SPECIFICATION

RATING/DESCRIPTION

CONDITION