Aux -64 – Yokogawa Value Series FX1000 User Manual
Page 77
2-64
IM 04L21B01-64EN
Aux
Log Input
• Display Digits
This setting is applied to any channels that are set to [LogType1] or [LogType2]. You
can set the number of digits in the mantissa of digital values to 2 or 3.
Example: If the number of mantissa display digits is 2, “1.2E+02.” If the number of
mantissa display digits is 3, “1.23E+02.”
• LogType2
This setting is applied to channels that are set to [LogType2]. If you set the channel
to input that is linear on a logarithmic scale, select [Linear]. If you set the channel to
pseudo logs, select [Pseudo].
Note
The setting of [LogType2] (Log Linear Input or Pseudo Log Input) is available if the FX1000
firmware version is R1.11 or later.
Power
• Phase and Wire system
You can set the phase and wire system to [1P2W] (single-phase two-wire system),
[1P3W] (single-phase three-wire system), or [3P3W] (three-phase three-wire system).
• Input voltage
When you have set the phase and wiring system to a value other than [1P3W], you
can set the rated input voltage to [120V] or [240V]. When you have set the phase and
wiring system to [1P3W], the rated input voltage is fixed to [240V].
2.6 Entering Basic Settings