beautypg.com

Calibration correction, Calibration correction -9, Index calibration correction – Yokogawa Value Series FX1000 User Manual

Page 22

background image

2-9

IM 04L21B01-64EN

Configuring the FX1000

1

2

3

8

Index

Calibration Correction

Set the input and output values for the calibration correction. The number of set points
(including the start and end points) can be specified in the range 2 to 16.

Click to delete the selected row.

Click to add set points (rows) to the number of calibration set points.

Input

Number of set points

Calibration set points

Y5
Y4

Y3
Y2

Y1

Output

X1 X2 X3 X4

X5

Condition

X1 < X2 < X3 < X4 < X5

Selectable Range of Input and Output Values

• Channels on which linear scaling is specified (SCALE)

–30000 to 30000 (the decimal place is the same setting as the scale value)

• Other channels (OFF, DELTA, SQRT, LogType1)

Value in the measurable range of the selected range
Example: –2.0000 to 2.0000 for 2 V range

Note

• When you set calibration correction on a channel that is set to LogType1 (nonlinear logs),

the set points are specified in the range of voltage values.

• You cannot set calibration correction on a channel that is set to LogType2.

2.3 Setting the Measurement Channels