• Relay AND

Select the relays that are to operate using AND logic. Set the range of relays (from

the first alarm relay) to take the AND logic. All subsequent relays will be set to OR
logic. Available settings are [None], [I01] (I01 only), [I01-I02] (I01 and I02), [I01-I03] (I01
to I03), etc. Only alarm output relays that are installed are valid.

• Relay action

Select whether the alarm output relay is energized or de-energized when an alarm

occurs. The setting applies to all alarm output relays.

• Relay hold

You can choose to make the alarm output relays behave in the following ways. This

setting applies to all relays.

Settings

Description

Unhold

Turns the output relay OFF when the alarm condition is released (returns to

normal condition).

Hold

Holds the output relay at ON until an alarm acknowledge operation is performed.

Relay Action on ACK

Settings

Description

Normal

The relay output is deactivated when the alarm ACK operation is executed. If the

condition for activating the alarm output relay is met in the next scan interval, the

relay output is activated.
This operation is valid only when the alarm output relay is set to [Hold].

Reset

The relay output is deactivated when the alarm ACK operation is executed. If a

new condition for activating the alarm output relay, the relay is activated.

Note

When reflash is turned ON, the operation of the first three output relays is set to nonhold.
Specifying Hold produces no effect.

Hysteresis

• Measure channel High/Low

Sets the hysteresis width of the alarm occurrence/release of the high/low limit alarm

specified on measurement channels.

Selectable range: 0.0% to 5.0% of the span or scaling width

• Measure channel Delta High/Low

Sets the hysteresis width of the alarm occurrence/release of the difference high/low

limit alarm specified on measurement channels.

Selectable range: 0.0% to 5.0% of the span

• Math channel High/Low

Sets the hysteresis width of the alarm occurrence/release of the high/low limit alarm

specified on computation and external input channels.

Selectable range: 0.0% to 5.0% of the measurement span

Alarm action

• No Logging

Select [ON] to hide alarm indication. The [Detect] setting is enabled in the [Measure

channel], [Math channel] tab(s).

This function disables the alarm indicator and the logging of alarm events to the alarm

summary.

2.6 Entering Basic Settings