Event data, Event data -30, Sample rate – Yokogawa Value Series FX1000 User Manual

Page 43: Mode, Data length, Pre-trigger, Trigger signal key

background image

2-30

IM 04L21B01-64EN

Event Data

Event related settings are enabled when [Data Kind] is set to [E+D] or [Event] in [Basic
Environment] under [Environment] in the [Basic Setting] tab.

Sample rate

Select the data recording interval from the available settings. See the description for “Data
length” below. You cannot specify a sampling rate that is faster than the scan interval.

Mode

Settings

Description

Free

Records data continuously.

Single

Records data when the trigger condition is met.

Repeat

Records data each time the trigger condition is met.

Data length

Select the size of a record data file. The recorded data is divided by the file size
specified here. The available data lengths vary depending on the number of memory
sampling channels and the Sample rate setting.

Sample rate

1

125 ms

250 ms

500 ms

1 s

2 s

Selectable range

of data length

10 min to

1 day

10 min to

2 days

10 min to

3 days

10 min to

7 days

10 min to

14 days

Sample rate

1

5 s

10 s

30 s

1 min

2 min

Selectable range

of data length

10 min to

31 days

10 min to

31 days

1 hour to

31 days

1 hour to

31 days

1 hour to

31 days

Sample rate

1

5 min

10 min

Selectable range

of data length

1 hour to

31 days

1 hour to

31 days

1 You cannot choose an interval that is faster than the scan interval.

Pre-Trigger

Specify the range when recording data before the trigger condition is met. Select the
range as a percentage of the data length from 0, 5, 25, 50, 75, 95, and 100%. If you do
not want to record the data existing before the trigger condition is met, select 0%.

Trigger Signal Key

Select [ON] if you want to activate the trigger using key operation.

2.5 Entering General Settings