PARAMETER SETTING/CONFIGURATION
V.
PARAMETER SETTING/CONFIGURATION
5.1
N
OTES
ON
THE
TBL
OPTIONAL
DIGITAL
DISPLAY
The TBL digital display may be used to set most of the parameters required to configure the
YEWFLO. In the Parameter list each item is marked to indicate whether that parameter can be set or
not. Due to the limited number of digits available in the TBL display, the full item identification is not
possible. Tables 5.1.1 and 5.1.2 describe the item numbers and their function on the TBL display.
Figure 5.1.1: Integral Indicator/Totalizer Display
Item
Description
•
Display section: Displays data, units, parameter setting item numbers, and
parameters.
‚
Setting section:
ƒ
Attach unit labels if those other than displayed units are to be used. Sets parameter
item numbers and parameter data using SET, SHIFT, and INC parameter
setting keys.
„
Decimal point
…
A symbol for delimiting a parameter setting item number and a parameter data
†
Setting key
Table 5.1.1: Mode Name List
Display Mode
Number
Name
Contents
0
%; display mode
Instantaneous flow rate is displayed as 0.0 to 110.0%.
1
Display in engineering unit mode
Instantaneous flow as an engineering unit is displayed using 0
to 32000.
2
Display in totalized flow mode
Totalized flow is displayed as 0 to 999999 without indicating the
decimal point.
3
Display alternates between % flow
rate and totalized flow mode
Instantaneous flow rate (%) and totalized flow (engineering unit)
are alternately displayed.
4
Display alternates between flow rate
in engineering units and totalized
flow mode
Instantaneous flow rate (engineering unit) and totalized flow rate
(engineering unit) are alternately displayed.
5
Display alternates between
instantaneous flow rates in
engineering unit and %
Instantaneous flow rates are alternately displayed as
engineering units and percentage (%).
Table 5.1.2: Description of display