Maintenance – Yokogawa digitalYEWFLO (DY) User Manual
Page 66

MAINTENANCE
IM 1F2B4-01-YIA
Page 70
4.1.12 Setting up the local LCD indicator display mode
The YEWFLO vortex meter offers a variety of display options. The following procedure will allow you to
select which values are displayed, for your application.
BT200 handheld terminal
BT100 handheld terminal
E: CONTROL
Scroll through the menus to
the E: CONTROL menu, then
press ENTER.
Press the MENU key until
the E: Control menu is
displayed.
E02: DISP SELECT
rate %
Scroll to parameter E02: DISP
SELECT then press ENTER.
Using the p r m tr key
move to parameter E02: Disp
Select .
Scroll to your desired choice,
press ENTER twice.
Using INC or DEC move
to the display option of your
choice, press ENT twice to
select.
Select one of the 6 display options for the local indicator.
The available options are:
rate %
Rate in percent of span.
rate
Rate in engineering units.
total
Totalized flow in engineering
units.
rate%, total
Alternating display; rate in
percent of span and total flow.
rate, total
Alternating display; rate in
engineering units total flow.
rate, rate%
Alternating display; rate in
engineering units and rate in
percent of span.