Appendix a: parameter details – Yokogawa digitalYEWFLO (DY) User Manual

Page 114

background image

Appendix A: Parameter Details

IM 1F2B4-01-YIA

Page 109

Hand Held

Terminal

Data Range

Indicator/Interface

Help / Remarks

Parameter No. and

Name

Prmtr

No.

Code No.

B08: Min. Density f

0.00001 to 32000

08

0.00001 to 32000 Enter the minimum flowing density using the units of

B07, this parameter works in conjunction with Noise
Judge to reject erroneous flow signals.

B09: Temp Unit

ºC
ºF

09

0
1

Select the temperature units.

B10: Temp f

-500.0 to 1000

10

-500.0 to 1000

Enter the operating Temperature in units of B09.

When the Fluid (parameter B04) is Steam M, Gas M, or Liq M complete B14 and B15 (otherwise not displayed).

B14: Density f

0.00001 to 32000

14

0.00001 to 32000 Enter the fluid density at operating conditions based on

the units of measure as specified in B07.

B15: Flow Unit

kg
ton
lb

15

0
1
2

Select the Mass flow units to be used.
ton = Metric Ton

When the Fluid (parameter B04) is Steam H complete B19 through B22 (otherwise not displayed).

B19: Density f

0.00001 to 32000

19

0.00001 to 32000 Enter the density of the fluid at operating conditions

based on the units of measure as specified in B07.

B20: Enthal Unit

Kcal / kg
KJ / kg
Btu / lb

20

0
1
2

Select the specific enthalpy units to be used.

B21: SPE Enthalpy

0.00001 to 32000

21

0.00001 to 32000 Enter value of specific enthalpy using the units

specified in B20.

B22: Flow Unit

kcal
Mcal
KJ
MJ
Btu

22

0
1
2
3
4

Select the energy flow units to be used.

When the fluid in B04 is Gas Qn complete B25 through B29 (otherwise not displayed).

B25: Temp n

-500.0 to 1000.0

25

-500.0 to 1000.0 Enter the temperature of the fluid at standard

conditions using the same units as specified in B09.

B26: Pressure f

0.00001 to 32000

26

0.00001 to 32000 Enter the operating pressure in absolute units.

B27: Pressure n

0.00001 to 32000

27

0.00001 to 32000 Enter the pressure at standard conditions in the same

units as used in B26.

B28: Deviation

0.00001 to 32000

28

0.00001 to 32000 Enter the ratio of compressibility at flowing conditions

to that at standard conditions. [ Z factor ]

B29: Flow Unit

Nm3
Nl
scf

29

0
1
2

Select the standard flow units to be used.
Scf reference temperature is 59°F;
Nm3 and Nl reference temperature is 0°C

When the fluid in B04 is Steam Qf, Gas Qf or Liq Qf complete B35 (otherwise not displayed)

B35: Flow unit

m3 (actual)
l (actual)
acf
US gal
UK gal

35

0

1
2
3
4

Select the flow units to be used.

B50: Time Unit

/ s
/ m
/ h
/ d

50

0
1
2
3

Select the proper time units for the flow span :
Note: when units of /s or /d are selected, neither the
flow unit nor the time unit is displayed on the local
indicator (/TBL).

B51: Span Factor

E 0

51

0

If the flow span to be entered in parameter B52 will be