TROUBLESHOOTING

6.5.2

Flowmeter output with no flow

Confirm that all downstream

valves are closed

Perform piping check-out

secion 6.4.3

END

END

END

YES

YES

YES

YES

YES

YES

YES

END

NO

NO

NO

NO

Are Analog/Pulse jumpers

set correctly and in agreement

with output type, parameter B2?

Do B parameters agree with

process conditions, fluid

type, meter size, etc.?

Perform noise balance

adjustment, section 6.4.4?

Output?

Perform noise judge adjustment,

section 6.4.5.

Output?

Perform trigger level

adjustment, section 6.4.6.

Output?

Perform low-cut frequency

adjustment, section 6.4.7.

Output?

Correct parameters

Correct parameters

NO

NO

END

END

Contact Yokogawa Industrial Automation

technical assistance, 800/524-7378