Maintenance – Yokogawa digitalYEWFLO (DY) User Manual
Page 67

MAINTENANCE
IM 1F2B4-01-YIA
Page 71
4.1.13 Setting the low cut flowrate
The low cut flowrate is a digital cut-off that can be configured to force the analog or pulse output to 0%
when the flow is below a predetermined value. This parameter is used especially to lock out erroneous
flow signals that may occur below Qmin, where it may be desirable to have the meter drop to zero rather
than provide erroneous readings.
To set the low cut flowrate; move to menu H: Maintenance , then move down to H07: L.C. Flowrate . Using
the numeric keypad input the low flow cut-off flowrate in flow span units. Once this value is stored, any
signal below the low cut flowrate will generate a 0% output.
H :Maintenance
BT200 handheld terminal
BT100 handheld terminal
H07 :L.C. Flowrate
10
Move to parameter H07, input the desired low flow cut-off value in flow span units,
i.e. 10 Gal/min.
Press Ente
r twice.
Press e
nt twice.
- EJA120A (79 pages)
- EJA130A (2 pages)
- EJA130A (4 pages)
- EJA120A (31 pages)
- EJA130A (47 pages)
- EJA120A (40 pages)
- EJA438 (5 pages)
- EJA120A (6 pages)
- EJA115 (85 pages)
- EJA120A (47 pages)
- EJA210A (70 pages)
- EJA130A (4 pages)
- EJA430A (78 pages)
- EJA210E (89 pages)
- EJA210E (170 pages)
- EJX120A (4 pages)
- EJA210E (9 pages)
- EJX115A (55 pages)
- EJA210E (41 pages)
- EJA210E (96 pages)
- EJA210E (52 pages)
- EJX910A (9 pages)
- EJX910A (103 pages)
- FlowNavigator Software (163 pages)
- EJX910A (55 pages)
- EJX910A (175 pages)
- EJX910A (83 pages)
- EJA530A (67 pages)
- EJA120A (83 pages)
- EJX530A (52 pages)
- EJA110E (4 pages)
- EJA110E (85 pages)
- EJX120A (85 pages)
- EJA118 (76 pages)
- EJX118A (64 pages)
- EJA438 (72 pages)
- EJA430E (85 pages)
- EJX430A (76 pages)
- EJA430E (7 pages)
- EJX430A (6 pages)
- EJX430A (40 pages)
- EJA430E (96 pages)
- EJA430E (41 pages)
- EJX438A (10 pages)
- ADMAG AXR (194 pages)