5 setting of switches(integral flowmeteronly), 1 setting of burnout switch, Setting of switches (integral flowmeter only) -8 – Yokogawa ADMAG AXF User Manual
Page 57: Setting of burnout switch -8, 5 setting of switches (integral flowmeter only)

IM 01E20D01-01E
5-8
5. MAINTENANCE
F0518-1.EPS
Clockwise 90
°
Display unit
mounting
screws
(two screws)
*1
Figure 5.4.2
Changing the Display Unit Direction 90
Degrees
IMPORTANT
*1: To preserve the safety, do not touch the
electrical circuit and cable of shaded area.
5.4.2.3
Installing the Cover
(1) Taking care not to entangle the cables, install the
cover to the flowmeter by turning it in the direc-
tion of the arrow as shown below.
(2) Tighten cover locking screw 1 counterclockwise
using a hexagonal wrench (nominal size 3) to lock
the cover.
F0518-2.EPS
Cover locking
screws
2
᭺
1
᭺
Figure 5.4.3
Installing the Display Cover
5.5 Setting of Switches
(Integral Flowmeter
Only)
IMPORTANT
• Removing and installing cover are necessary
for setting switches. Perform removing and
installing of the cover as described in section
5.4.2.1 and 5.4.2.3.
• To preserve the safety, do not touch the
electrical circuit and the cables except setting
switches.
5.5.1
Setting of Burnout Switch
The burnout function sets the direction of current
output in situations where the CPU has become
damaged. Upon shipment from the manufacturing
plant, the burnout direction is set to High (i.e., 25 mA);
however, in cases where the optional code C1 has been
specified, the output direction will be set to Low (i.e.,
0 mA).
Modification of the burnout direction must be carried
out using the setting switch from the amplifier’s CPU
board (i.e., Switch 1) (See Figure 5.5.1).
Table 5.5.1
Output Setting Pins for Burnout
T0501.EPS
Position of
Pin
Burnout
Direction
Burnout
Output
Remarks
Low
High
Low
High
Low
High
0 mA
25 mA
Set to Low for optional
code C1
Set to High before
shipment
NOTE
• On the amplifier’s CPU board, the burnout
setting switch (i.e., Switch 1) and the write
protect switch (i.e., Switch 2) are located
adjacent to each other. Accordingly, special
care should be taken when making switch
settings.
• In the case of Fieldbus communication type,
burnout setting swich is not applied.