<10. General Specifications>

10-2

IM 01C25R01-01E

Output specifications for HART Protocol Type “◊”

Output

Dual output (Both analog and pulse/contact

output can be obtained simultaneously).

In this case refer to the item “Wiring example for

analog output and status/pulse output”.
HART Protocol Revision

HART protocol revision can be selected from 5

or 7 when ordering.

The protocol revision can be changed by user

configuration.

Note: Protocol revision supported by HART

configuration tool must be the same or higher

than that of the EJX multivariable transmitter.

Protocol revision supprted

by HART configuration tool

5

7

Protocol revision of

EJX multivariable

transmitter.

5





7

Í





: Communication OK

Í

: Communication NG

Analog Output

Two wire 4 to 20 mA DC output, user-selectable

for Differential Pressure, Static Pressure,

External Temperature or Flow Rate signal.
Failure Alarm

• Analog output status at CPU failure and

hardware error

Up-scale: 110%, 21.6 mA DC or more

(standard)

Down-scale: –2.5%, 3.6 mA DC or less

• Analog output status at process abnormality

(Option code /DG6);

The result of process abnormality detected

by the advanced diagnostic function can

be reflected to an analog alert status. The

following three setting modes are available.

Mode

Burnout

Fall back

Off

Standard

110%, 21.6mA or more

Holds to a

specified

value withun

the output

range from

3.8mA to

21.6mA

Normal

output

Option

Code

/C1 -1.25%, 3.8mA or less

/C2 -1.25%, 3.8mA or less

/C3 103.1%, 20.5mA or more

Pulse/Contact Output

Pulse or status output is selected by parameter

setting.

Transistor contact output (sink type).

Contact rating:

10.5 to 30 V DC, 120 mA DC max.

Low level: 0 to 2 V DC. (See figure below for

high and low levels (pulse output).)

HIGH level

LOW level

0 to 2 V

0V

F1001.ai

Pulse Output

Scaled pulse or frequency pulse output is

selected by parameter setting.
Scaled Pulse Output Function

Pulse is output by the unit of the scaled flow rate.

Scaled pulse can be totalized.
Frequency Output Function

Number of pulses output per second at 100% of

output.

Pulse frequency: Max. 10 kHz

Duty cycles: Approx. 50% (1:2 to 2:1)

Contact Output Function

High or low alarm

Status signal output mode can be reversed

(ON/OFF).
Signal Output (for HART protocol type)

Output

Flow

rate*

1

Differential

pressure

Static

pressure

External

temperature

Total

flow*

1

4-20mA

*

3

*

2

Pulse output

High/Low

alarm

*1:

When Measurement Function Code B is specified.

*2:

Square root output is not available. Low cut linear

mode is not supported.

*3:

Reversed output is not available.