beautypg.com

Installation, 1 precautions, 2 mounting – Yokogawa EJX930A User Manual

Page 30: Installation -1, Precautions -1, Mounting -1, Important

background image

<5. Installation>

5-1

IM 01C25R01-01E

5. Installation

5.1 Precautions

Before installing the transmitter, read the cautionary

notes in section 3.4, “Selecting the Installation

Location.” For additional information on the

ambient conditions allowed at the installation

location, refer to subsection 10.1 “Standard

Specifications.”

IMPORTANT

• When welding piping during construction,

take care not to allow welding currents to

flow through the transmitter.

• Do not step on this instrument after

installation.

5.2 Mounting

■ The transmitter is shipped with the process

connection, according to the ordering

specifications. To change the orientation of the

process connections, refer to section 5.3.

■ With differential pressure transmitters,

the distance between the impulse piping

connection ports is usually 54 mm (figure 5.1).

By changing the orientation of the process

connector, the dimension can be changed to 51

mm or 57 mm.

■ The transmitter can be mounted on a nominal

50 mm (2-inch) pipe using the mounting bracket

supplied, as shown in figure 5.2 and 5.3.

The transmitter can be mounted on either a

horizontal or a vertical pipe.

■ When mounting the bracket on the transmitter,

tighten the (four) bolts that hold the transmitter

with a torque of approximately 39 N·m {4kgf·m}.

57 mm

54 mm

51 mm

F0501.ai

Figure 5.1

Process Connector Impulse Piping

Connection Distances for multivariable

Transmitters

F0502.ai

Horizontal pipe mounting

Vertical pipe mounting

Transmitter

mounting bolt

U-bolt nut

Mounting bracket

U-bolt nut

Mounting bracket

50 mm(2-inch) pipe

50 mm(2-inch) pipe

U-bolt

U-bolt

Transmitter

mounting bolt

Figure 5.2

Transmitter Mounting (Horizontal

Impulse Piping Type)

This manual is related to the following products: