beautypg.com

1 configuration procedure for basic mode, 2 calculation of the basic mode parameters, Configuration procedure for basic mode -6 – Yokogawa EJX930A User Manual

Page 14: Calculation of the basic mode parameters -6

background image

<2. About the EJX Multivariable Transmitter>

2-6

IM 01C25R01-01E

2.5.1 Configuration Procedure for Basic

Mode

Either a communicator or the mass flow

configuration software is required to carry out

configuration in basic mode.
Calculation of the basic mode parameters is

necessary to perform configuration. Following

shows the procedures for HART protocol type.
(1) Have ready a power supply, a personal

computer, a HART modem and the FSA120

EJX-MV Configuration DTM.

(2) Install the flow configuration software on the

personal computer.

This is not necessary if only the HART

communicator is used for configuration.

(3) Connect the EJX multivariable transmitter to the

power supply.

NOTE

Even when the RTD is not connected and alarm

number 03 is displayed on the indicator, setting

can be performed.

(4) Connect the HART communicator or the HART

modem to the transmitter.

(5) Perform flow configuration.

(6) Execute flow simulation with the HART HHT

or the FSA120 software in order to confirm the

configured flow parameters.

When the simulation is carried out, it is

necessary to connect the RTD or mock

resistance (about 100Ω) to the transmitter.

Input the differential pressure, static pressure,

and temperature values and then confirm that

the desired flow has been obtained.

(7) Remove the HART communicator or the HART

modem from the transmitter.

(8) Turn off the power supply.

NOTE

(1) Refer to the following instruction manuals for

more detailed explanation.

Setting with the HART HHT:

IM01C25R02-01E.

Setting with the Fieldbus configuration tool:

IM01C25R03-01E.

Setting with the FSA120: IM01C51R01-01E.

(2) For the flow configuration in the field after

installation, perform only steps 4 to 7.

2.5.2 Calculation of the Basic mode

parameters

There are two methods for the calculation of the

Basic mode parameters.
Method 1: Calculating the Kfactor by flow

parameters

Method 2: Calculating the Kfactor by means of the

flow condition

Method 1. Calculating the Kfactor by flow

parameters.

(1) Selection of the flow equation

Select the desired operational expression

according to the fluid type and the flow unit

category shown in Table 2.1.

(2) Confirming the unit

The unit to be used in this calculation is as

follows:

Differential pressure: Pa

Static Pressure: kPa abs

Temperature: K

The dimension of the pressure unit Pa are

M•L

-1

•S

-2

Where M: mass (Kg)

L: Length (m)

S: Time (second)

(3) Preparation of flow parameters for Kfactor

calculation

Each parameter must be expressed in the

following units.

d: m,

ρb and ρnorm: Kg/m

3

C, β, ε and K has no dimensions

(4) Calculation of the unit conversion coefficient Nc

The flow rate value does not change

automatically when a flow unit parameter is set

for the transmitter, and is always output as Kg/s

(mass flow). M

3

/s (volume flow), Nm

3

/s (Normal

volume flow.)

In order to obtain a value in your designated

unit, it is necessary to set Nc.

Nc is a conversion coefficient for the flow and

DP unit that is designated to be used.

(5) Selection of the Kfactor equation and calculation

Select the Kfactor expression according to the

fluid type and the unit category shown in Table

2.1.

Calculate the Kfactor using the parameters and

the expression.

This manual is related to the following products: