2 wiring installation, 6 rtd cable connection, Wiring installation -4 – Yokogawa EJX930A User Manual
Page 41: Rtd cable connection -4 7.6.1, Connecting shielded cable with cable gland
<7. Wiring>
7-4
IM 01C25R01-01E
7.5.2 Wiring Installation
(1) General-use Type and Intrinsically Safe
Type
With the cable wiring, use a metallic conduit or
waterproof glands.
• Apply a non-hardening sealant to the terminal
box connection port and to the threads on the
flexible metal conduit for waterproofing.
F0710.ai
Flexible metal conduit
Wiring metal
conduit
Tee
Drain plug
Apply a non-hardening
sealant to the threads
for waterproofing.
Figure 7.8
Typical Wiring Using Flexible Metal
Conduit
(2) Flameproof Type
Wire cables through a flameproof packing adapter,
or use a flameproof metal conduit.
■ Wiring cable through flameproof packing adapter.
• Apply a non-hardening sealant to the terminal
box connection port and to the threads on the
flameproof packing adapter for waterproofing.
Flameproof packing adapter
Flexible metal conduit
Wiring metal
conduit
Tee
Drain plug
Apply a non-hardening
sealant to the threads
for waterproofing.
F0711.ai
Figure 7.9
Typical Cable Wiring Using Flameproof
Packing Adapter
■ Flameproof metal conduit wiring
• A seal fitting must be installed near the terminal
box connection port for a sealed construction.
• Apply a non-hardening sealant to the threads of
the terminal box connection port, flexible metal
conduit and seal fitting for waterproofing.
F0712.ai
Non-hazardous area
Hazardous area
Flameproof
heavy-gauge
steel conduit
Tee
Drain plug
Seal fitting
Gas sealing device
Flameproof flexible
metal conduit
Apply a non-hardening
sealant to the threads
of these fittings for
waterproofing
After wiring, impregnate the fitting
with a compound to seal tubing.
Figure 7.10 Typical Wiring Using Flameproof Metal
Conduit
7.6 RTD Cable Connection
Connection of the RTD cable is always required
to measure external temperature. Follow the
procedures below to connect and disconnect a
cable when a cable gland or a conduit is used.
7.6.1 Connecting Shielded Cable with
Cable Gland
(External temperature input code:
-1, -2, -3, and -4)
• RTD connection components: EJX multivariable
transmitter, two cable glands, and RTD cable
Two cable glands are attached.
Y
L
P
P
U
S
ESL
UP
K
C
E
H
C
M
R
A
L
A
Transmitter
Cable gland
Electrical connection
RTD cable
with connector
Detail of connector
F0713.ai