5 totalizer function block, Totalizer function block -9 – Yokogawa EJX115A User Manual
Page 69
<9. Parameter Lists>
9-9
IM 01C25T04-01EN
9.5 Totalizer Function Block
Relative
Index
Index
Parameter
Write
Mode
Initial Value
Explanition
0
16
BLOCK_OBJECT
—
—
Information on this block such as Profile, Profile Rev, etc.
1
17
ST_REV
—
0
The revision level of the static data associated with the
function block. The revision vsalue will be incremented each
time a static parameter value in the block is changed
2
18
TAG_DESC
AUTO
Space
The user description of the intended application of the
block.
3
19
STRATEGY
AUTO
0
The strategy field can be used to identify grouping of block.
This data is not checked or processed by the block.
4
20
ALERT_KEY
AUTO
0
The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
5
21
TARGET_MODE
AUTO
AUTO
Set the Target of block mode to Auto or O/S according to the
write mode of the parameter to be set or changed
6
22
MODE_BLK
—
AUTO
The mode parameter is a structured parameter composed
of the actual mode, the normal mode, and the permitted
mode.
7
23
ALARM_SUM
—
—
The current alarm status associated with the function block
8
24
BATCH
AUTO
—
This parameter is intended to be used in Batch application
according to IEX 61512-1.
9
25
TOTAL
MAN
—
This parameter contains the integrated quantity of the rate
parameter provided by CHANNEL and the associated
status.
10
26
UNIT_TOT
AUTO
1034: m3
Unit of the totalized quantity.
11
27
CHANNEL
O/S
0x0158: Calculate
Value
Reference to the active Transducer Block, which provides
the measurement value to the Function Block.
12
28
SET_TOT
AUTO
0: TOTALIZE
Reset of the internal value of the FB algorithm to 0 or set
this value to PRESET_TOT.
13
29
MODE_TOT
AUTO
3: HOLD
This parameter governs the behavior of the totalization.
14
30
FAIL_TOT
AUTO
0: RUN
Fail-safe mode of the Totalizaer Function Block. This
parameter governs the behavior of the Function Block
during the occurrence of input value with BAD status.
15
31
PRESET_TOT
AUTO
0
This value is used as present for the internal value of the FB
algorithm. The value gets effective if using the SET_TOT
function.
16
32
ALARM_HYS
AUTO
0
Amount the PV must return within the alarm limits before
the alarm condition clears. Alarm Hysteresis is expressed in
engineering unit.
17
33
HI_HI_LIM
AUTO
+1.#INF
Value for upper limit alarms.
18
34
HI_LIM
AUTO
+1.#INF
Value for upper limit warnings.
19
35
LO_LIM
AUTO
-1.#INF
Value for lower limit warnings.
20
36
LO_LO_LIM
AUTO
-1.#INF
Value for lower limit alarms.
21
37
HI_HI_ALM
—
—
State of the upper limit of alarms.
22
38
HI_ALM
—
—
State of the upper limit of warnings.
23
39
LO_ALM
—
—
State of the lower limit of warnings.
24
40
LO_LO_ALM
—
—
State of the lower limit of alarms.