Yokogawa EJX115A User Manual
Page 62
<9. Parameter Lists>
9-2
IM 01C25T04-01EN
Relative
Index
Index
Parameter
Write
Mode
Initial Value
Explanation
22
38
DEVICE_INSTAL_
DATE
AUTO
Date of installation of the device.
23
39
LOCAL_OP_ENA
AUTO
1: Enabled
Local operation enable.
0: Disabled
1: Enabled
24
40
IDENT_NUMBER_
SELECTOR
AUTO
127: Adaptation
Mode
The parameter to select Ident number.
0:Profile specific (Transmitter 3 AI)
1:Manufacturer specific (Ident number of DEVICE_ID)
127: Adaptation Mode
128: Profile specific 2 (Transmitter 1 AI)
129: Profile specific 3 (Transmitter 12 AI)
130: Profile specific 4 (Transmitter 1 AI+TOT)
131: Profile specific 5 (Transmitter 2 AI+TOT)
132: Profile specific 6 (Transmitter 3 AI+TOT)
140: Manufacturer specific (If EJA, Ident number of EJX)
25
41
HW_WRITE_
PROTECTION
—
0
Indicates the position of a write blocking mechanism which
can not be modified by remote access which protects
parameter modification of a device.
0:Unprotected
2:Protected
26
42
FEATURE
—
—
Indicates optional feature implemented in the device and
the status of these features which indicates if the feature is
supported or not supported.
27
43
COND_STATUS_
DIAG
AUTO
Condensed Status
and Diagnosis
information is
provided
Indicates the mode of a device that can be configured for
stats and diagnostic behavior.
0: Status and Diagnosis
1: Condensed Status and Diagnosis information is
provided
33
49
SOFT_DESC
—
“2.40 - 4581 - 1.01” Yokogawa internal use only
34
50
SET_ADDRESS
AUTO
0
For Bus address set up
35
51
SIM_ENABLE_MSG
AUTO
Software switch for simulation function
36
52
DEVICE_STATUS_1
AUTO
0x00000000
Device status
37
53
DEVICE_STATUS_2
AUTO
0x00000000
Device status
38
54
DEVICE_STATUS_3
AUTO
0x00000000
Device status
39
55
DEVICE_STATUS_4
AUTO
0x00000000
Device status
40
56
DEVICE_STATUS_5
AUTO
0x00000000
Device status
41
57
DEVICE_STATUS_6
AUTO
0x00000000
Device status
42
58
DEVICE_STATUS_7
AUTO
0x00000000
Device status
43
59
DEVICE_STATUS_8
AUTO
0x00000000
Device status
44
60
DIAGNOSIS_SIM_
MODE
AUTO
0: Disabled
For testing alarms and warnings can be modified. Switch to
enable or disable alarm simulation. When this parameter is
set to enable and the hardware simulation jumper is on, all
of alarms and warnings in DIAGNOSIS_EXTENSION can
be modified with DIAGNOSIS_SIM_EXTENSION.
0: Disabled
1: Enabled
45
61
DIAGNOSIS_SIM_
EXTENSION
AUTO
0x00, 0x00, 0x00,
0x00
For testing alarms and warnings can be modified. When
the hardware simulation jumper is on, DIAGNOSIS_SIM_
MODE is set to enable, and the bits are set to “on”, the
arlarms (or warnings) can be modified. (0x000000000000)
46
62
DIAGNOSIS_MASK_
EXTENSION_RW
AUTO
0xff, 0x3c, 0x33,
0xf0, 0x00, 0x00
Set masked DIAGNOSIS_EXTENSION.
When DIAGNOSIS_MASK_EXTENSION_RW-bit is
ON and its alarm or warning occurs, its DIAGNOSIS_
EXTENSION-bit is ON.
47
63
SI_CONTROL_
CODES
—
0
A parameter for switching to make the instrument
compatible with SI units.
48
64
IDENT_NUMBER
—
—
Ident number of the device
64
80
PRIVATE_1
—
—
Not used for the transmitter
65
81
PRIVATE_2
—
—
Not used for the transmitter
66
82
PRIVATE_3
—
—
Not used for the transmitter
67
83
PRIVATE_4
—
—
Not used for the transmitter
68
84
PRIVATE_5
—
—
Not used for the transmitter
69
85
PRIVATE_6
—
—
Not used for the transmitter
70
86
PRIVATE_7
—
—
Not used for the transmitter
71
87
PRIVATE_8
—
—
Not used for the transmitter