25
41
PROCESS_
CONNECTION_TYPE
O/S
Unknown
Index code for the material of the process connection. The
coding is in accordance to the Material Codes given in
teneral Requirements.
26
42
PROCESS_
CONNECTION_
MATERIAL
O/S
Unknown
Material code for the type of process connection. The index
code is manufacturer specific.
27
43
TEMPERATURE
—
—
Temperature with the associated status used within the
transducer.
28
44
TEMPERATURE_
UNIT
O/S
1001: deg C
The unit of the temperature.
29
45
SECONDARY_
VALUE_1
—
—
Pressure value and status available to the Function Block.
30
46
SECONDARY_
VALUE_1_UNIT
O/S
kPa
Pressure unit of the SECONDARY_VALUE_1
33
49
LIN_TYPE
O/S
0: Linear
Type of linearization
0: Linear
1: Linearization table
10: Square root
34
50
SCALE_IN
AUTO
—
This is the input conversion using the high and low scale.
The related unit is the SECONDARY_VALUE_1_UNIT.
35
51
SCALE_OUT
AUTO
Output conversion of the linearized value using the high and
low scale. The related unit is the PRIMARY_VALUE_UNIT.
It is in accordance to the table of units codes given in the
general requirements.
36
52
LOW_FLOW_
CUTOFF
O/S
0
This is the point in percent of flow until the output of the flow
function is set to zero. It is used for suppressing low flow
values.
38
54
TAB_ACTUAL_
NUMBER
0
The actual numbers of entries in the table. It shall be
calculated after the transmission of the table is finished.
39
55
TAB_ENTRY
O/S
0
This parameter identifies which element of the table is in the
TAB_X_Y_VALUE parameter currently
40
56
TAB_MAX_NUMBER
31
Maximum size of the table in the device
41
57
TAB_MIN_NUMBER
2
Minimum size of the table in the device
42
58
TAB_OP_CODE
O/S
0: not initialized
The modification of a table in a device influences the
measurement or actuation algorithms of the device. This
parameter is to control the transaction of the table.
43
59
TAB_STATUS
—
0
Result of plausibility check in the device
44
60
TAB_X_Y_VALUE
O/S
One value couple of the table
59
75
PRIMARY_VALUE_
URL
—
100
Upper limit of primary value
60
76
PRIMARY_VALUE_
LRL
—
-100
Lower limit of primary value
61
77
SENSOR_SN
—
Serial number of sensor
62
78
SENSOR_CAL_
METHOD
O/S
103: Factory trim
standard calibration
The method of the last sensor calibration
100= volumetric
101= static weight
102= dynamic weight
103= factory trim standard calibration
104= user trim standard calibration
105= factory trim special calibration
106= user trim special calibration
255= other
63
79
SENSOR_CAL_LOC
O/S
Space
Set/indicate the location of the last sensor calibration
64
80
SENSOR_CAL_DATE O/S
—
Set/indicate the date of the last sensor calibration
65
81
SENSOR_CAL_WHO O/S
Space
Set/indicate the name of the person responsible for the last
sensor calibration
66
82
STATIC_PRESSURE_
HIGH_VALUE
—
—
67
83
STATIC_PRESSURE_
UNIT
O/S
kPa
Unit of static pressure
68
84
CAL_DEVIATION_HI
O/S
0
Deviation value for span adjustment
69
85
CAL_DEVIATION_LO O/S
0
Deviation value for zero adjustment
70
86
PRIMARY_VALUE_
FTIME
O/S
2
Damping time constant for primary value