Yokogawa EJX115A User Manual
Page 53
<8. Diagnostic Information>
8-7
IM 01C25T04-01EN
ALARM
Display
Cause of
Alarm
SENSOR Transducer block
NAMUR
NE107
Category
Pressure Value
Primary Value
Calculated Value
Static Pressure Value Capsule Temp
Amplifier Temperature
Value
Status
Value
Status
Value
Status
Value
Status
AL.93
AI MAN
AI1 block is
MAN mode
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C
AL.94
AI MAN
AI2 block is
MAN mode
AL.95
AI MAN
AI3 block is
MAN mode
AL.96
STB.SIM
Simulation
function of
Sensor TB is
active
[Simulation
start]
UNCERTAIN:
Simulated
value, start
[Simulation
finished
(<10s)]
UNCERTAIN:
Simulated
value, end
AL.97
PB SIM
Simulation
function of
Physical block
is active
GOOD (NC):
OK
AL.72
TOT
MAN
Totalizer
Functiion block
is MAN mode
AL.60
STB.
CFG
SENSOR
Transducer
block
configuration
Error
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C