Yokogawa EJX115A User Manual
Page 65
<9. Parameter Lists>
9-5
IM 01C25T04-01EN
Relative
Index
Index
Parameter
Write
Mode
Initial Value
Explanation
71
87
STATIC_PRESSURE_
LOW_VALUE
—
—
72
88
SP_VALUE_TYPE
O/S
109: absolute
pressure
Select the type of measurement for static pressure,
absolute or gauge
73
89
SP_VALUE_URL
—
25000
Upper limit of static pressure value
74
90
SP_VALUE_LRL
—
0
Lower limit of static pressure value
75
91
CAL_SP_POINT_HI
O/S
25000
The highest calibrated value for static pressure
76
92
CAL_SP_POINT_LO
O/S
0
The lowest calibrated value for static pressure
77
93
CAL_SP_MIN_SPAN
—
500
The minimum calibrated span allowed for static pressure
78
94
CAL_SP_
DEVIATION_HI
O/S
0
Deviation value for zero adjustment of static pressure
79
95
CAL_SP_
DEVIATION_LO
O/S
0
Deviation value for span adjustment of static pressure
80
96
SP_VALUE_FTIME
O/S
2
Damping time constant for static pressure
81
97
ATM_PRESS
O/S
101.325
Atmoshpere pressure value used to obtain gauge pressure
value from absolute pressure
82
98
CLEAR_CAL
O/S
0
Reset zero and span adjustment to factory calibrated
values for pressure, static pressure and or all
83
99
TEMPERATURE_
VALUE_URL
—
130
Upper limit of temperature value
84
100
TEMPERATURE_
VALUE_LRL
—
-50
Lower limit of temperature value
85
101
AMP_TEMP_VAL
—
—
Value of amplifier temperature
86
102
AMP_TEMP_URL
—
95
Upper limit of amplifier temperature value
87
103
AMP_TEMP_LRL
—
-50
Lower limit of amplifier temperature value
88
104
CALCULATE_VALUE —
—
Calculation result of (Primary Value) × (Calculate
Coefficient)
89
105
CALCULATE_UNIT
O/S
1347 (m3/s)
Unit of CALCULATE_VALUE
90
106
CALCULATE_COEF
O/S
1
Coefficient for calculating Calculate Value (CALCULATE_
VALUE). Calculate Coefficient can be considered as
K-factor for flow rate calculation.
91
107
MODEL
—
Space
The model code
92
108
SPECIAL_ORDER_ID —
Space
Identification number of special order
93
109
MANUFAC_DATE
O/S
0, 0, 0, 0, 0, 0
Date of production
94
110
D_VENT_PLUG
O/S
Unknown
material of drain or vent plug
95
111
REM_SEAL_ISOL_
MTL
O/S
Unknown
Material of isolating diaphragm for remote seal
96
112
FLANGE_SIZE
O/S
Unknown
Flange size for remote seal
97
113
REM_SEAL_NUM
O/S
Unknown
Number of remote seal
98
114
REM_SEAL_FILL_
FLUID
O/S
Unknown
Type of fill fluid in remote seal
99
115
REM_SEAL_TYPE
O/S
Unknown
Type of remote seal
100
116
AUTO_RECOVERY
O/S
1 (ON)
Permission of auto recovery from sensor errors
101
117
MS_CODE
AUTO
—
Model suffix and code
102
118
SIMULATE_MODE
AUTO
0
Mode of simulation
103
119
SIMULATE_VALUE
AUTO
—
Value written by an operator to simulate Transducer Block
value
141
157
CURVE_X
AUTO
—
Parameter for signal charactrization
142
158
CURVE_Y
AUTO
—
Parameter for signal charactrization
158
174
TEST_KEY1
—
—
Not used for the transmitter
159
175
TEST_KEY2
—
—
Not used for the transmitter
160
176
TEST_KEY3
—
—
Not used for the transmitter
161
177
TEST_1
—
—
Not used for the transmitter
162
178
TEST_2
—
—
Not used for the transmitter
163
179
TEST_3
—
—
Not used for the transmitter
164
180
TEST_4
—
—
Not used for the transmitter
165
181
TEST_5
—
—
Not used for the transmitter
173
189
TEST_13
—
—
Not used for the transmitter
174
190
TEST_14
—
—
Not used for the transmitter
175
191
TEST_15
—
—
Not used for the transmitter