5 local display, 1 procedure to set the integral indicator, Local display -11 5.5.1 – Yokogawa EJX115A User Manual
Page 31: Procedure to set the integral indicator -11
<5. Parameter Setting>
5-11
IM 01C25T04-01EN
5.5 Local Display
5.5.1 Procedure to Set the Integral Indicator
F0505.ai
Corresponding
decimal point
Engineering Unit
Eng. Unit @ 1/10
Eng. Unit @ 1/100
Eng. Unit @ 1/1000
LCD value
(kPa)
Exponent
2
23.46
2
2.35
2
0.23
2
0.02
Select from Parameter Displays (1-4)
(Display Selection)
Select items to be displayed in the lower text field
(Information Selection)
Specify whether DISPLAY1, DISPLAY2, DISPLAY3, or
DISPLAY4 should be displayed.
Specify whether tag, parameter, unit, or status should be
displayed.
Select parameters to be displayed.
Written as by 6 characters or 6 characters plus “/”,“.”.(*1)
Written as by 6 characters or 6 characters plus “/”,“.”.(*1)
Specify parameters to be displayed
(Parameter Selection)
Perform ON/OFF setting of the bar graph
(Bar Graph)
Set the display period
(Display Cycle)
Time unit: 400ms; When the value set is “7”, the same
display continues for about 2.8 seconds.
Example display of exponent setting:
The LCD value for exponent setting when the actual
pressure value is 23.4568 kPa and the decimal point
selected is 2.
Set an exponent
(Exponent Mode)
Set the display contents for the block tag to be displayed in
the lower text field
(Display Tag)
Set the display contents
of the unit
(Display unit)
Select whether the unit to be displayed in the lower text field
should be set to automatic or on a customized basis
(Unit Selection)
CUSTOM is
selected
AUTO is
selected
*1:
Combination of up to 6 characters of alphanumeric and the symbols of [/], [.] and [ ] (space) are available.
If the other characters are specified, space will be displayed.
The symbols of [/] and [.] cannot be specified on the head of a string.
Figure 5.3
Procedures to Set the Built-in Display