Parameter lists, 1 physical block, Parameter lists -1 – Yokogawa EJX115A User Manual
Page 61: Physical block -1
<9. Parameter Lists>
9-1
IM 01C25T04-01EN
9. Parameter Lists
Note: The Write Mode column contains the modes in which each parameter is write enabled.
O/S:
Write enabled in O/S mode.
MAN: Write enabled in Man mode and O/S mode.
AUTO: Write enabled in Auto mode, Man mode, and O/S mode.
—:
Read only.
9.1 Physical Block
Relative
Index
Index
Parameter
Write
Mode
Initial Value
Explanation
0
16
BLOCK_OBJECT
—
—
Information on this block such as Profile, Profile Rev, etc.
1
17
ST_REV
—
—
The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.
2
18
TAG_DESC
AUTO
PT1001
The user description of the intended application of the
block.
3
19
STRATEGY
AUTO
0
The strategy field can be used to identify grouping of block.
This data is not checked or processed by the block.
4
20
ALERT_KEY
AUTO
0
The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
5
21
TARGET_MODE
AUTO
AUTO
Set the Target of block mode to Auto or O/S according to the
write mode of the parameter to be set or changed.
6
22
MODE_BLK
AUTO
—
The mode parameter is a structured parameter composed
of the actual mode, the normal mode, and the permitted
mode.
7
23
ALARM_SUM
—
—
The current alarm status associated with the function block.
8
24
SOFTWARE_
REVISION
—
Revision number of the software of the field device.
9
25
HARDWARE_
REVISION
—
Revision number of the hardware of the field device.
10
26
DEVICE_MAN_ID
—
Yokogawa
Identification code of the manufacturer of the field device.
11
27
DEVICE_ID
—
EJX: EJX
EJA: EJA
Manufacturer specific identification of the field device.
12
28
DEVICE_SER_NUM
—
Serial number of field device.
13
29
DIAGNOSIS
—
0x00, 0x00, 0x00,
0x00
Detailed information of the devices, bitwise coded. More
than one message possible at once.
14
30
DIAGNOSIS_
EXTENSION
—
0x00, 0x00, 0x00,
0x00, 0x00, 0x00
Additional manufacture-specific information of the device,
bitwise coded.
15
31
DIAGNOSIS_MASK
—
Condensed Status:
0x00, 0x98, 0x0F,
0x80
Definition of supported DIAGNOSIS informatiion-bits.
0: not supported
1: supported
16
32
DIAGNOSIS_MASK_
EXTENSION
—
0xff, 0x3c, 0x37,
0xf2, 0x00, 0x00
Difinition of supported DIAGNOSIS_EXTENSION
information-bits.
0: not supported
1: supported
17
33
DEVICE_
CERTIFICATION
—
Not used for the trasnmitter.
18
34
WRITE_LOCKING
AUTO
Off
If set, no writes from anywhere are allowed, except for
to clear WRITE_LOCK. Block inputs will continue to be
updated.
0: on(Locked)
2457: off(Not Locked)
19
35
FACTORY_RESET
AUTO
1: Factory Reset
Allows a manual restart to be initiated.
1: Factory Reset (Resetting device for default values. The
Bus Address setting remains the same.)
2506: Warm start (Warm start of the device. All
parameterization remains unchanged.)
2712: Reset Address to '126' (Reset the Bus Address
only.)
20
36
DESCRIPTOR
AUTO
User difinition text (a string) to describe the device within
the application.
21
37
DEVICE_MESSAGE
AUTO
User difinable MESSAGE (a string) to describe the device
within the application or in the plant.