Yokogawa EJX115A User Manual
Page 60

<8. Diagnostic Information>
8-14
IM 01C25T04-01EN
ALARM
Display
Cause of
Alarm
AI1 Output Value (Channel = Primary Value)
Totalizer Value (Channel = Calculate Value) NAMUR
NE107
Category
FSAFE_TYPE
= 0
FSAFE_TYPE
= 1
FSAFE_TYPE
= 2
FSAFE_TYPE
= 0
FSAFE_TYPE
= 1
FSAFE_TYPE
= 2
AL.40
PB O/S
Physical block
is O/S mode
BAD:
Out of Service
BAD:
Out of Service
BAD:
Out of Service
UNCERTAIN:
Non specific ok
limit
UNCERTAIN:
Last Usable
Value const
limit
UNCERTAIN:
Non specific ok
limit
---
AL.41
STB O/S
SENSOR
Transducer
block is O/S
mode
UNCERTAIN:
Substitute
Value
UNCERTAIN:
Last Usable
Value
BAD:
Non-specific
AL.43
AI O/S
AI1 function
block is O/S
mode
BAD:
Out of Service
Constant
BAD:
Out of Service
BAD:
Out of Service
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
AL.44
AI O/S
AI2 function
block is O/S
mode
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
AL.45
AI O/S
AI3 function
block is O/S
mode
AL.72
TOT O/S
Totalizer
function block
is O/S mode
BAD:
Out of Service
BAD:
Out of Service
BAD:
Out of Service
AL.50
P.SDEV
P.ZDEV
Trimming
range error
for differential
pressure span
UNCERTAIN:
Engineering
Unit Range
Violation
UNCERTAIN:
Engineering
Unit Range
Violation
UNCERTAIN:
Engineering
Unit Range
Violation
UNCERTAIN:
engineering
unit violation
UNCERTAIN:
engineering
unit violation
UNCERTAIN:
engineering
unit violation
C
AL.51
SP.SDEV
SP.ZDEV
Trimming
range error
for static
pressure span
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
AL.79
LCD.
RNG
Displayed
value exceeds
limit or LCD
configuration
error
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
---
AL.90
AI SIM
Simulation
function of AI1
block is active
UNCERTAIN:
Simulated
Value
UNCERTAIN:
Simulated
Value
UNCERTAIN:
Simulated
Value
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
C
AL.91
AI SIM
Simulation
function of AI2
block is active
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
AL.92
AI SIM
Simulation
function of AI3
block is active
AL.93
AI MAN
AI1 block is
MAN mode
UNCERTAIN:
Simulated
Value Constant
UNCERTAIN:
Simulated
Value Constant
UNCERTAIN:
Simulated
Value Constant
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
C
AL.94
AI MAN
AI2 block is
MAN mode
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
AL.95
AI MAN
AI3 block is
MAN mode
AL.96
STB.SIM
Simulation
function of
Sensor TB is
active
UNCERTAIN:
Simulated
Value
UNCERTAIN:
Simulated
Value
UNCERTAIN:
Simulated
Value
UNCERTAIN:
Simulated
Value
UNCERTAIN:
Simulated
Value
UNCERTAIN:
Simulated
Value
AL.97
PB SIM
Simulation
function of
Physical block
is active
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
AL.72
TOT
MAN
Totalizer
Functiion block
is MAN mode
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
UNCERTAIN:
Simulated
Value Constant
UNCERTAIN:
Simulated
Value Constant
UNCERTAIN:
Simulated
Value Constant
AL.60
STB.
CFG
SENSOR
Transducer
block
configuration
Error
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
C