<8. Diagnostic Information>
8-9
IM 01C25T04-01EN
ALARM
Display
Cause of
Alarm
SENSOR Transducer block
NAMUR
NE107
Category
Pressure Value
Primary Value
Calculated Value
Static Pressure Value Capsule Temp
Amplifier Temperature
Value
Status
Value
Status
Value
Status
Value
Status
AL.40
PB O/S
Physical block
is O/S mode
Measured
Value
BAD: non
specific
Measured
Value
BAD: non
specific
Measured
Value
BAD: non
specific
Measured
Value
BAD: non
specific
---
AL.41
STB O/S
SENSOR
Transducer
block is O/S
mode
BAD: out of
service
BAD: out of
service
BAD: out of
service
BAD: out of
service
AL.43
AI O/S
AI1 function
block is O/S
mode
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
GOOD (NC):
OK
AL.44
AI O/S
AI2 function
block is O/S
mode
AL.45
AI O/S
AI3 function
block is O/S
mode
AL.72
TOT O/S
Totalizer
function block
is O/S mode
AL.50
P.SDEV
P.ZDEV
Trimming
range error
for differential
pressure span
Measured
Value
UNCERTAIN:
engineering
unit violation
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C
AL.51
SP.SDEV
SP.ZDEV
Trimming
range error for
static pressure
span
GOOD (NC):
OK
UNCERTAIN:
engineering
unit violation
AL.79
LCD.
RNG
Displayed
value exceeds
limit or LCD
configuration
error
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
---
AL.90
AI SIM
Simulation
function of AI1
block is active
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C
AL.91
AI SIM
Simulation
function of AI2
block is active
AL.92
AI SIM
Simulation
function of AI3
block is active
AL.93
AI MAN
AI1 block is
MAN mode
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C
AL.94
AI MAN
AI2 block is
MAN mode
AL.95
AI MAN
AI3 block is
MAN mode
AL.96
STB.SIM
Simulation
function of
Sensor TB is
active
UNCERTAIN:
Simulated
Value
AL.97
PB SIM
Simulation
function of
Physical block
is active
GOOD (NC):
OK
AL.72
TOT
MAN
Totalizer
Functiion
block is MAN
mode
AL.60
STB.
CFG
SENSOR
Transducer
block
configuration
Error
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
Measured
Value
GOOD (NC):
OK
C