Lat4] [hys4, Setup-output, Hysteresis 4 – Watlow Series 988 User Manual

Page 57: Latching 4

background image

4.30

WATLOW Series 988 User’s Manual

Setup Menus, Chapter 4

Setup-Output

Hysteresis 4

Select the switching hysteresis for alarm 4. This determines the change
in temperature or process units needed to turn the output from off to on.

• If [`AL4] is set to [rAtE] settings for [HYS4] will be in degrees per
minute or units per minute.

• If the input referenced by [`AL4] is set to [`r†d] the range is affected as
listed below.

[HYS4] This prompt appears only on controllers equipped with output 4
hardware for a relay (98_ _-_ _ _ _-_B_ _, 98_ _-_ _ _ _-_D_ _ ,
98_ _-_ _ _ _-_E_ _ or 98_ _-_ _ _ _-_K_ _) or switched dc (98_ _-_ _ _ _-_C_ _).

If

Default

[``°F]

[```1]

[```3]

[`999]

[`C_F]

[HYS4]

[HYS4]

[HYS4]

(Global Menu)

[``°F]

&

[`r†d]

[``)1]

[``#0]

[`9(9]

[`C_F]

Input 1 or 2

[HYS4]

[HYS4]

[HYS4]

(Global Menu)

(see note above)

[``°C]

[```1]

[```2]

[`555]

[`C_F]

[HYS4]

[HYS4]

[HYS4]

(Global Menu)

[``°C]

&

[`r†d]

[``)1]

[``@0]

[`5%5]

[`C_F]

Input 1 or 2

[HYS4]

[HYS4]

[HYS4]

(Global Menu)

(see note above)

[```1]

[```3]

[`999]

units

a process input

[HYS4]

[HYS4]

[HYS4]

is selected

Latching 4

Select whether alarm 4 will be latching or non-latching. A latching
alarm [`LAT] must be turned off manually. A non-latching alarm [`nLA]
turns off when an alarm condition no longer exists.

[LAt4] This prompt appears only on controllers equipped with output 4
hardware for a relay (98_ _-_ _ _ _-_B_ _, 98_ _-_ _ _ _-_J_ _ or
98_ _-_ _ _ _-_K_ _) or switched dc (98_ _-_ _ _ _-_C_ _). and with [`Ot4] set
to [`AL4] or [AL4n].

Default

[`nLA]

[`LAt]

[LAt4]

[LAt4]

˜

NOTE:
See

Chapter 7

for

more information
on alarms.

[LAt4]

[HYS4]