Output 2 (p. 4.21), P. 4.21, Ot2] [prc2 – Watlow Series 988 User Manual
Page 48: Setup-output, Output 2, Process 2

WATLOW Series 988 User’s Manual
4.21
Setup Menus, Chapter 4
Setup-Output
Output 2
Set the way that output 2 will respond to a difference between the set
point and an input variable.
• [`AL2] de-energizes output 2 in an alarm condition.
• [AL2n] energizes output 2 in an alarm condition.
• [``Ht] select reverse action, so that output 2 responds when the input
signal is less than the set point.
• [``CL] select direct action, so that output 2 responds when the input
signal is more than the set point.
[`Ot2] This prompt appears only on controllers equipped with output 2
hardware (not 98_ _-_ _ _A-_ _ _ _). [`AL2] and [AL2n] do not appear if out-
put 2 is a process output (98_ _-_ _ _F-_ _ _ _). [``Ht] and [``CL] do not
appear if [AL90] (in the Global Menu) is set to [dUPL].
Default
↓
[``no]
[`AL2]
[Al2n]
[``Ht]
[``CL]
[`Ot2]
[`Ot2]
[`Ot2]
[`Ot2]
[`Ot2]
Process 2
Select the process range for output 2.
[Prc2] This prompt appears only on controllers equipped with output 2
process hardware (98_ _-_ _ _F-_ _ _ _) and with [`Ot2] not set to [``no].
Default
↓
4-20mA
0-20mA
0-5V
Î
1-5V
Î
0-10V
Î
(dc)
[4-20]
[0-20]
[`0-5]
[`1-5]
[0-10]
[Prc2]
[Prc2]
[Prc2]
[Prc2]
[Prc2]
[`Ot2]
[Prc2]