2.15

Installation and Wiring, Chapter 2

Figure 2.15b —

Switched DC, Open Collector

98 _ _ - _ _ _ _ - _ C _ _

Maximum voltage: 42VО

О (dc)

Maximum current: 1A

Figure 2.15a —

AC Outputs

Solid-state Relay

with Contact Suppression

98 _ _ - _ _ _ _ - _ B _ _

0.5 amps, minimum off-state impedance: 20K

Electromechanical Relay

with Contact Suppression

(Suppression between NO and COM contacts only)

98 _ _ - _ _ _ _ - _ D _ _ _

Form C, 5 amps, minimum off-state impedance: 20K

Electromechanical Relay

without Contact Suppression

98 _ _ - _ _ _ _ - _ E _ _ _

Form C, 5 amps, off-state impedance: 31M

Solid-state Relay

without Contact Suppression

98 _ _ - _ _ _ _ - _ K _ _ _

0.5 amps, off-state impedance: 31M

Output 4 Wiring

External

Load

COM

L1

L2

Fuse

NO

5

6

NC

(#7 for D & E outputs only)

7

5

External

Load

6

+

7

-

COM

Figure 2.15c —

External Signal Conditioner Power Supply

98 _ _ - _ _ _ _ - _ T _ _

5

6

+

-

+V

-V

Transmitter

4-20mA out

Input
1 or 2

+

-

For data communications wiring refer to

Data Communications

with the Watlow Series 988 Family of Controllers.

NOTE:
Input-to-output iso-
lation is defeated
when the external
transmitter power
supply is used to
power a signal con-
ditioner connected
to input 1 or input 2.

˜

NOTE:
See Chapter 1 for
power supply DIP
switch information.

NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(

Appendix

);

• DIP switch set-
tings (

Chapter 1

);

• Sensor match
(

Chapter 2

and

Appendix

);

• Sensor installation
(

Chapter 2

); and

• Wiring (

Chapter 2

).

+

Internal Circuitry

5

6

7

790

19 to 32V

Î

(dc)

NOTE:
Switching inductive
loads (relay coils,
solenoids, etc.) with
the mechanical
relay or solid state
relay output options
requires using an
R.C. suppressor.
Watlow carries the
R.C. suppressor
Quencharc brand
name, which is a
trademark of ITW
Paktron. Watlow
Part No. 0804-0147-
0000.

Loop powered