beautypg.com

Output 3 wiring, Process retransmit, External signal conditioner power supply – Watlow Series 988 User Manual

Page 24: Ac outputs, Switched dc

background image

Figure 2.14c —

Process Retransmit

0-20mA, 4-20mA, Load impedance: 600

max.

98 _ _ - _ _ _ _ - M _ _ _

0-5VО

О, 1-5VО

О, 0-10VО

О (VDC), Load impedance: 500

min.

98 _ _ - _ _ _ _ - N _ _ _

2.14

WATLOW Series 988 User’s Manual

Installation and Wiring, Chapter 2

NOTE:
Input-to-output iso-
lation is defeated
when the external
signal conditioner
power supply is
used to power a
transmitter con-
nected to input 1 or
input 2.

NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(

Appendix

);

• DIP switch set-
tings (

Chapter 1

);

• Sensor match
(

Chapter 2

and

Appendix

);

• Sensor installation
(

Chapter 2

); and

• Wiring (

Chapter 2

).

Figure 2.14d —

External Signal Conditioner Power Supply

98 _ _ - _ _ _ _ - T _ _ _

Figure 2.14a —

AC Outputs

Solid-state Relay

with Contact Suppression

98 _ _ - _ _ _ _ - B _ _ _

0.5 amps, minimum off-state impedance: 20K

Electromechanical Relay

without Contact Suppression

98 _ _ - _ _ _ _ - J _ _ _ _

Form A or B, 5 amps, off-state impedance: 31M

Solid-state Relay

without Contact Suppression

98 _ _ - _ _ _ _ - K _ _ _ _

0.5 amps, off-state impedance: 31M

External

Load

COM

L1

L2

Fuse

NO Form A

1

2

NC Form B

or

Figure 2.14b —

Switched DC

98 _ _ - _ _ _ _ - C _ _ _

Minimum load resistance: 500

1

2

External

Load

-

+

1

2

+

-

+V

-V

Transmitter

4-20mA out

Input

1 or 2

+

-

Form A

Form A or B
alarm jumper
settings (98__-
____-J___ only)

˜

NOTE:
See Chapter 1 for
power supply DIP
switch information.

+

Internal Circuitry

1

2

790

19 to 32V

Î

(dc)

1

2

+

-

Output 3 Wiring

NOTE:
Switching inductive
loads (relay coils,
solenoids, etc.) with
the mechanical
relay or solid state
relay output options
requires using an
R.C. suppressor.
Watlow carries the
R.C. suppressor
Quencharc brand
name, which is a
trademark of ITW
Paktron. Watlow
Part No. 0804-0147-
0000.

Loop powered

Form B