Hys2] [sp2c, Setup-output, Hysteresis 2 – Watlow Series 988 User Manual
Page 49: Set point 2 control
4.22
WATLOW Series 988 User’s Manual
Setup Menus, Chapter 4
Setup-Output
Hysteresis 2
Select the switching hysteresis for output 2. This determines the
change in temperature or process units needed to turn the output from off
to on.
• If [`AL2] is set to [rAtE] settings for [HYS2] will be in degrees per
minute or units per minute.
• If the input referenced by [`AL2] is set to [`r†d] the range is affected as
listed below.
[HYS2] This prompt appears only on controllers equipped with output 2
hardware and with the controller set up as an on/off controller ([Pb2A} =
[```0]), and with [`Ot2] not set to [``no]. This prompt does not appear
on controllers equipped with output 2 process hardware, ([`In2} = [sLid],
or if [ALg0} in the Global menu = [dUPL]).
If
Default
↓
↓
[``°F]
[```1]
…
[```3]
…
[`999]
[`C_F]
[HYS2]
[HYS2]
[HYS2]
(Global Menu)
[``°F]
&
[`r†d]
[``)1]
…
[``#0]
…
[`9(9]
[`C_F]
Input 1 or 2
[HYS2]
[HYS2]
[HYS2]
(Global Menu)
(see note above)
[``°C]
[```1]
…
[```2]
…
[`555]
[`C_F]
[HYS2][
HYS2]
[HYS2]
(Global Menu)
[``°C]
&
[`r†d]
[``)1]
…
[``@0]
…
[`5%5]
[`C_F]
Input 1 or 2
[HYS2]
[HYS2]
[HYS2]
(Global Menu)
(see note above)
[```1]
…
[```3]
…
[`999]
units
a process input
[HYS2]
[HYS2]
[HYS2]
is selected
Set Point 2 Control
Select a second set point.
• [``Pr] enables a set point independent from the Set Point 1 [`SP1]
value.
• [``dE] enables a set point at a deviation from the Set Point 1 [`SP1]
value.
[Prc1] This prompt appears only if output 2 hardware is present and is
equal to the output 1 setting.
Default
↓
[``Pr]
[``dE]
[SPc2]
[SPc2]
[HYS2]
[SP2c]