beautypg.com

Model number information – Watlow Optimizing Your Process System with the Series 988 Controller User Manual

Page 68

background image

7.11

Optimizing Your Process System with the WATLOW Series 988

How to Choose the Right 988 to Fit Your Application

Series 988/989 Model Number Information

98 _ _ - _ _ _ _ - _ _ _ _

Hardware
6 = Vertical mounting, 24-28 V
7 = Horizontal mounting, 24-28 V
8 = Vertical mounting, 100-240 V
9 = Horizontal mounting, 100-240 V
Software
A = Standard
B = Enhanced (with cascade, ratio, dual PID, differential)
#1 Input
1 = Basic thermocouple signal conditioner

(excluding Type R, S and B)

2 = Universal signal conditioner
#2 Input
0 = None
1 = Basic thermocouple signal conditioner

(excluding Type R, S and B)

2 = Universal signal conditioner
3 = Slidewire feedback
4 = Current transformer
5 = Second digital event (one digital event is standard on all units)
#1 Output
B = Solid state relay, Form A, 0.5A, with RC suppression
C = Switched DC, open collector, isolated
D = *Electromechanical relay, Form C, 5A, with RC supression
E = *Electromechanical relay, Form C, 5A, without RC suppression
F = Universal process, 0-5VDC, 1-5VDC, 0-10VDC, 0-20mA, 4-20mA
K = Solid state relay, Form A, 0.5A, without RC suppression
#2 Output
A = None
B = Solid state relay, Form A, 0.5A, with RC suppression
C = Switched DC, open collector, isolated
D = *Electromechanical relay, Form C, 5A, with RC suppression
E = *Electromechanical relay, Form C, 5A, without RC suppression
F = Universal process, 0-5VDC, 1-5VDC, 0-10VDC, 0-20mA, 4-20mA
K = Solid state relay, Form A, 0.5A, without RC suppression
T = External signal conditioner power supply, 5, 12 or 20VDC @ 30mA
#3 Output
A = None
B = Solid state relay, Form A, 0.5A, with RC suppression
C = Switched DC, open collector, isolated
J = *Electromechanical relay, Form A or B, 5A, without RC suppression
K = Solid state relay, Form A, 0.5A, without RC suppression
M = Retransmit, 0-20mA, 4-20mA
N = Retransmit, 1-5VDC, 0-10VDC, 0-5VDC
T = External signal conditioner power supply, 5, 12 or 20VDC @ 30mA
#4 Output
A = None
B = Solid state relay, Form A, 0.5A, with RC suppression
C = Switched DC, open collector, isolated
D = *Electromechanical relay, Form C, 5A, with RC suppression
E = *Electromechanical relay, Form C, 5A, without RC suppression
K = Solid state relay, Form A, 0.5A, without RC suppression
R = Isolated RS-232 communications
S = Isolated EIA-485/RS-422 communications
T = External signal conditioner power supply, 5, 12 or 20VDC @ 30mA
Display Color (Upper/Lower)
GG = Green/Green
GR = Green/Red
RG = Red/Green
RR = Red/Red

Sensor Ranges

J t/c:

32

to

1500

°F

0

to

816

°C

K t/c:

-328

to

2500

°F

-200

to 1371

°C

T t/c:

-328

to

750

°F

-200

to

399

°C

N t/c:

32

to

2372

°F

0

to 1300

°C

R t/c:

32

to

3200

°F

0

to 1760

°C

S t/c:

32

to

3200

°F

0

to 1760

°C

B t/c:

1598

to

3300

°F

870

to 1816

°C

E t/c:

-328

to

1470

°F

-200

to

799

°C

C t/c:

32

to

4200

°F

0

to 2316

°C

D t/c:

32

to

4200

°F

0

to 2316

°C

Pt 2:

32

to

2543

°F

0

to 1395

°C

1

°RTD (JIS): -328 to 1166°F

-200

to

630

°C

1

°RTD (DIN): -328 to 1472°F

-200

to

800

°C

0.1

°RTD (JIS

and DIN): -99.9 to 999.9

°F

-73.3

to 537.7

°C

0-5VDC:

-999

to

9999

1-5VDC:

-999

to

9999

0-10VDC:

-999

to

9999

0-20mA:

-999

to

9999

4-20mA:

-999

to

9999

0-50mVDC:

-999

to

9999

0-100mVDC: -999

to

9999

Slidewire:

100

to

1200

Current:

0

to

50mA

Potentiometer:

0

to

1200

*Electromechanical relays are not recom-
mended for PID control. They are warranted
for only 100,000 contact closures

100