Differential, Enhanced software features – Watlow Optimizing Your Process System with the Series 988 Controller User Manual
Page 37
Optimizing Your Process System with the WATLOW Series 988
Enhanced Software Features
4.4
Differential
Overview
Differential control allows the Series 988 to
control one process at a difference to another
process. Input 2 acts as a remote set point
input. However the displayed set point indi-
cates the desired difference between input 1
and input 2. The set point to which input 1 will
control to is determined by the equation:
internal set point = input 2 + differential set point
The lower display shows the differential set
point, which can be adjusted with the incre-
ment (up-arrow) and decrement (down-arrow)
keys.
Please note that while in the differential control
mode the set point for input 1 cannot be viewed
and must be calculated with the equation.
Requirements
Two inputs and the enhanced software option
are required.
TL
TL
W
WA
PROCESS
L1
L2
L3
L4
DEV
% OUT
DISPLAY
MODE
AUTO
MAN
SERIES 988
limit
sensor
heating element
input 1
input 2
temperature
sensor
outside
temperature
sensor
output 1
limit
Water Boiler
Sample Application
The most common application using differential control is to maintain water
temperature in a boiler at a differential to the outside air temperature. A
thermocouple at input 2 senses the outside air temperature and adjusts the
internal set point to maintain the boiler water temperature 120 degree higher.
Substituting values we have: boiler temperature = outside temperature + 120
°
.
In this application the system uses two, type J thermocouples: one to sense
boiler water temperature (input 1) and one to sense the outside air tempera-
ture (input 2).
To configure the controller, first enable input 2 (set
to J). To enable the
differential control algorithm set the control prompt
in the Global menu
to differential
. Press the DISPLAY key. The lower display will read 0,
indicating no differential between input 1 and input 2. Adjust the set point to
120. The internal set point for input 1 is now equal to the input 2 value plus
120, which will maintain the boiler water temperature 120 degrees higher
than the outside air temperature.