Standard Features

5.3

Optimizing Your Process System with the WATLOW Series 988

TL

TL

W

WA

PROCESS

L1

L2

L3

L4

DEV

% OUT

DISPLAY

MODE

AUTO

MAN

SERIES 988

temperature
sensor

Alarm

input 1

output 1

output 2

form C relay

Oven

heaters

The temperature is within the normal range.
Output 2 is inactive.

5-Silencing
Alarm silencing overrides the alarm at power
up, and it allows the operator to silence an
alarm with the system still in an alarm condi-
tion. The silencing is active until the process
has entered the safe region located between the

limit

limit
sensor

TL

TL

W

WA

PROCESS

L1

L2

L3

L4

DEV

% OUT

DISPLAY

MODE

AUTO

MAN

SERIES 988

Alarm

temperature
sensor

limit
sensor

input 1

output 1

output 2

form C relay

Oven

heaters

An over-temperature condition activates output 2,
which turns the alarm on.

limit

Sample Application

An operator is using a deviation alarm to keep a process within +/- 5

°F of

the set point. Output 2 is set up as a deviation alarm that activates a
buzzer. However, when the process powers up in the morning, the process
temperature is below the low deviation alarm set point, causing the buzzer
to sound until the process reaches the low alarm set point. Selecting ON

at the silencing prompt

in the Output menu, disables the alarm

output controlling the buzzer until the process gets within the deviation
alarm set points. It also allows the operator to silence the buzzer by
pressing the AUTO/MAN key once, if an alarm does occur.

low and high alarm settings. Any future devia-
tion outside the safe region triggers an alarm. If
the alarm occurs at this point, the output can
be silenced by pressing the AUTO/MAN key
once, but the alarm message is still displayed.