Optimizing Your Process System with the WATLOW Series 988

General Software Features

3.8

Input Filter

Overview

In certain applications the process being
measured can be unstable, which makes it
difficult to control and also makes the con-
stantly changing display difficult to read. The
Series 988 input filter can solve these problems
by smoothing out just the display or the display
and the input signal.

You can set a time constant, in seconds, for a

TL

W

WA

PROCESS

L1

L2

L3

L4

DEV

% OUT

DISPLAY

MODE

AUTO

MAN

SERIES 988

limit

limit
sensor

input 2

input 1

heater

output 1

temperature
sensor

Humidity Chamber

Display readings with input
filter off

Display readings with input
filter on

time

time

%RH

%RH

humidity
transmitter

Sample Application

A Series 988 controls the humidity in an environmental chamber. The
relative humidity (RH) sensor provides a 4-20mA signal over a 0-100% RH
range. The sensor is very sensitive to changes caused by air flow in the
chamber. The turbulence in the chamber has the 988 display jumping two
to three percent. To remove this display dithering the filter time constant

for input 1 is set to 2 seconds. This will smooth the display and

provide a more realistic reading.

low-pass filter that will affect the display only,
or you can configure the option to filter the
input signal itself. Use this feature with cau-
tion, because a large time constant could hide
system upsets.

Requirements

This feature is standard on all Series 988
controllers.