Chapter 7 Features

Lockout Security [rLoC] to 5 and Set Lockout Se-

curity [SLoC] to 0.

4. The operator wants to read and write to the Home

Page and Profiling Page, and lock all other pages

and menus.

In the Factory Page, Lockout Menu, set Read Lock-

out Security [rLoC] to 2 and Set Lockout Security
[SLoC]

to 2.

In the Factory Page, Lockout Menu, set Lock Op-

erations Page [LoC;O] to 3 and Lock Profiling Page
[LoC;P]

to 2.

5. The operator wants to read the Operations Page,

Setup Page, Profiling Page, Diagnostics Menu,

Lock Menu, Calibration Menu and Custom Menus.

The operator also wants to read and write to the

Home Page.

In the Factory Page, Lockout Menu, set Read Lock-

out Security [rLoC] to 1 and Set Lockout Security
[SLoC]

to 5.

In the Factory Page, Lockout Menu, set Lock Op-

erations Page [LoC;O] to 2 and Lock Profiling Page
[LoC;P]

to 3.

Using Password Security

It is sometimes desirable to apply a higher level of

security to the control where a limited number of

menus are visible and not providing access to others

without a security password. Without the appropri-

ate password those menus will remain inaccessible. If

Password Enabled [pas;e] in the Factory Page under

the [`loC] Menu is set to on, an overriding Password

Security will be in effect. When in effect, the only Pag-

es that a User without a password has visibility to are

defined in the Locked Access Level [loC;L] prompt.

On the other hand, a User with a password would

have visibility restricted by the Read Lockout Security
[rloC]

. As an example, with Password Enabled and

the Locked Access Level [loC;L] set to 1 and [rloC]

is set to 3, the available Pages for a User without a

password would be limited to the Home and Factory

Pages (locked level 1). If the User password is entered

all pages would be accessible with the exception of the

Setup Page as defined by level 3 access.
How to Enable Password Security
Go to the Factory Page by holding down the Infinity
ˆ

key and the Advance

key for approximately six

seconds. Once there, push the Down ¯ key one time to

get to the [`loC] menu. Again push the Advance

key

until the Password Enabled [pas;e] prompt is visible.

Lastly, push either the up or down key to turn it on.

Once on, 4 new prompts will appear:
1. [loC;l], Locked Access Level (1 to 5) correspond

ing to the lockout table above.
2. [roll], Rolling Password will change the Cus-

tomer Code every time power is cycled.
3. [pas;u], User Password which is needed for a Us-

er to acquire access to the control.
4. [pas;a], Administrator Password which is need-

ed to acquire administrative access to the control.
The Administrator can either change the User and

or the Administrator password or leave them in the

default state. Once Password Security is enabled they

will no longer be visible to anyone other than the Ad-

ministrator. As can be seen in the formula that follows

either the User or Administrator will need to know

what those passwords are to acquire a higher level of

access to the control. Back out of this menu by push-

ing the Infinity ˆ key. Once out of the menu, the Pass-

word Security will be enabled.
How to Acquire Access to the Control
To acquire access to any inaccessible Pages or Menus,

go to the Factory Page and enter the [UloC] menu.

Once there follow the steps below:
Note:
If Password Security (Password Enabled [pas;e] is

On) is enabled the two prompts mentioned below in

the first step will not be visible. If unknown, call the

individual or company that originally setup the con-

trol.
1. Acquire either the User Password [pas;u] or the

Administrator Password [pas;a].
2. Push the Advance

key one time where the Code

[Code] prompt will be visible.
Note:

a. If the the Rolling Password is off push the Ad-

vance key one more time where the Password

[pass] prompt will be displayed. Proceed to
either step 7a or 8a. Pushing the Up ¿ or Down

¯ arrow keys enter either the User or Adminis-

trator Password. Once entered, push and hold

the Infinity ˆ key for two seconds to return to

the Home Page.
b. If the Rolling Password [roll] was turned on

proceed on through steps 3 - 9.

3. Assuming the Public Key [Code] prompt is still

visible on the face of the control simply push the

Advance Key

to proceed to the Password [pass]

prompt. If not find your way back to the Factory

Page as described above.
4. Execute the calculation defined below (7b or 8b) for

either the User or Administrator.
5. Enter the result of the calculation in the upper dis-

play by using the Up ¿ or Down ¯ arrow keys or

use EZ-ZONE Confgurator Software.
6. Exit the Factory Page by pushing and holding the

Infinity ˆ key for two seconds.
Formulas used by the User and the Administrator to

calculate the Password follows:
Passwords equal:
7. User
a. If Rolling Password [roll] is Off, Password

[pass] equals User Password [pas;u].