Watlow EZ-ZONE

®

ST

45

Chapter 4 Setup Page

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

&

Read/

Write

[t;tUn]
[t.tUn]

Control Loop (1)

TRU-TUNE+™ Enable

Enable or disable the

TRU-TUNE+™ adaptive

tuning feature.

[``no]

No (59)

[`YES}

Yes (106)

No

Instance 1

Map 1 Map 2

257

1780

0x97 (151)

1

10 (16)

- - - -

8022 Inst. 1

1922

uint

RWES

[t;bnd]
[t.bnd]

Control Loop (1)

TRU-TUNE+™ Band

Set the range, centered

on the set point, within

which TRU-TUNE+™ will

be in effect. Use this func-

tion only if the controller

is unable to adaptive tune

automatically.

0 to 100

0

Instance 1

Map 1 Map 2

307

1782

0x97 (151)

1

0x11 (17)

- - - -

8034 Inst. 1

1946

uint

RWES

[`t;gn]
[ t.gn]

Control Loop (1)

TRU-TUNE+™ Gain

Select the responsiveness

of the TRU-TUNE+™

adaptive tuning calcula-

tions. More responsive-

ness may increase over-

shoot.

1 to 6

3

Instance 1

Map 1 Map 2

308

1784

0x97 (151)

1

0x12 (18)

- - - -

8035 Inst. 1

1948

uint
RWES

[t;Agr]
[t.Agr]

Control Loop (1)

Autotune Aggressive-

ness

Select the aggressiveness

of the autotuning calcula-

tions.

[Undr]

Under damped (99)

[Crit]

Critical damped (21)

[OuEr]

Over damped (69)

Critical

Instance 1

Map 1 Map 2

259

1786

0x97 (151)

1

0x13 (19)

- - - -

8024 Inst. 1

1926

uint
RWES

[`UFA]
[UFA]

Control Loop (1)

User Failure Action

Select what the controller

outputs will do when the

user switches control to

manual mode.

[`oFF]

Off, sets output power

to 0% (62)

[bPLS]

Bumpless, maintains

same output power, if it was

less than 75% and stable, oth-

erwise 0% (14)

[MAn]

Manual Fixed, sets

output power to Manual

Power setting (33)

[USEr]

User, sets output pow-

er to last open-loop set point

the user entered (100)

User

Instance 1

Map 1 Map 2

213

1912

0x6B

(107)

1

0xC (12)

- - - -

7012 Inst. 1

2182

uint
RWES

[FAiL]
[FAiL]

Control Loop (1)

Input Error Failure

Select what the controller

outputs will do when an

input error switches con-

trol to manual mode.

[`oFF]

Off, sets output power

to 0% (62)

[bPLS]

Bumpless, maintains

same output power, if it was

less than 75% and stable, oth-

erwise 0% (14)

[MAn]

Manual Fixed, sets

output power to Manual

Power setting (33)

[USEr]

User, sets output pow-

er to last open-loop set point

the user entered (100)

User

Instance 1

Map 1 Map 2

214

1914

0x6B

(107)

1

0xD (13)

- - - -

7013 Inst. 1

2184

uint
RWES

Note:
Some values will be rounded off to fit in the four-character display .

Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EE-

PROM

S:

User

Set