Current menu – Watlow EZ-ZONE ST User Manual
Page 52
Watlow EZ-ZONE
®
ST
•
50
•
Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[A;dSP]
[A.dSP]
Alarm (1 to 2)
Display
Display an alarm message
when an alarm is active.
[`oFF]
Off (62)
[``on]
On (63)
On
Instance 1
Map 1 Map 2
- - - - 1480
Instance 2
Map 1 Map 2
- - - - 1540
0x6D
(109)
1 to 2
0x10 (16)
30
9016 Inst. 1
1510
Inst. 2
1560
uint
RWES
[`A;dL]
[ A.dL]
Alarm (1 to 2)
Delay
Set the span of time that
the alarm will be delayed
after the process value ex-
ceeds the alarm set point.
0 to 9,999 seconds
0
Instance 1
Map 1 Map 2
- - - - 1490
Instance 2
Map 1 Map 2
- - - - 1550
0x6D
(109)
1 to 2
0x15 (21)
31
9021
- - - - uint
RWES
[CUrr]
[`Set]
Current Menu
[`C;Sd]
[ C.Sd]
Current (1)
Sides
Select which side or sides
will be monitored.
[`oFF]
Off (62)
[high]
High (37)
[low]
Low (53)
[both]
Both (13)
Off
Instance 1
Map 1 Map 2
283
1248
0x73 (115)
1
5
145
15005 Inst. 1
1128
uint
RWES
[`C;Ur]
[ C.Ur]
Current (1)
Message Enable
Display under/ over range
current.
No (59)
Yes (106)
No
Instance 1
Map 1 Map 2
- - - - 1246
0x73 (115)
1
4
146
15004 Inst. 1
1126
uint
RWES
[`C;le]
[ C.LE]
Current (1)
Current Limit Trip En-
able
No (59)
Yes (106)
No
Instance 1
Map 1 Map 2
284
1250
0x73 (115)
1
6
- - - -
15006 Inst. 1
1130
uint
RWES
[C;;oFs]
[C.oFS]
Current (1)
Heater Offset
Apply an offset to the cur-
rent reading
-9,999.000 to 9,999.000
0.0
Instance 1
Map 1 Map 2
- - - - 1260
0x73 (115)
1
0xB (11)
149
15011 Inst. 1
1140
float
RWE
No Dis-
play
Current (1)
Current Gain
-1,999.000 to 9,999.000
100.0
Instance 1
Map 1 Map 2
290
1258
0x73 (115)
1
0xA (10)
- - - -
- - - - Inst. 1
1138
float
RWE
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EE-
PROM
S:
User
Set