beautypg.com

Standard bus eia-485 communications, Modbus rtu or standard bus eia-485 communications – Watlow EZ-ZONE ST User Manual

Page 26

background image

Ó

Warning:

Use National Electric (NEC)

or other country-specific

standard wiring and safety

practices when wiring and

connecting this controller to

a power source and to elec-

trical sensors or peripheral

devices . Failure to do so may

result in damage to equip-

ment and property, and/or

injury or loss of life .

NOTE: To prevent ground

loops, isolation needs to be

maintained from input to out-

put when using switched DC

or analog process outputs .

CAUTION: Always mount the

controller with the heat-sink

fins aligned vertically .

NOTE: Terminals L4 and

A1 on the limit connector

are jumpered at the factory

to complete the contactor

circuit . Additional switches

may be wired in series to the

terminals .

Ó

WARNING: If high voltage is

applied to a low-voltage con-

troller, irreversible damage

will occur .

Watlow EZ-ZONE

®

ST

24

Chapter 2 Install and Wire

Note: Excessive writes to

EEPROM over Modbus can

cause premature EEPROM

failure . The EEPROM is rated

for 1,000,000 writes . See

"Saving Settings to Nonvola-

tile Memory" in Chapter 2,

Install and Wire .

Standard Bus EIA-485 Communications

T-/R-

common

98
99

CF

CD
CE

B5
D6
D5

Slot C

T+/R+

• Wire T-/R- to the A terminal of

the EIA-485 port.

• Wire T+/R+ to the B terminal of

the EIA-485 port.

• Wire common to the common

terminal of the EIA-485 port.

• Do not route network wires

with power wires. Connect net-

work wires in daisy-chain fash-

ion when connecting multiple

devices in a network.

• Do not connect more than 16

controllers on a network.

• maximum network length:

1,200 meters (4,000 feet)

• 1/8th unit load on EIA-485 bus
ST _ _ - _ _ * _ - _ _ _ _

* All models include Standard Bus

communications

Modbus RTU or Standard Bus EIA-485 Communications

Modbus RTU or

Standard Bus EIA-485

T-/R-

common

98
99

CC
CA
CB

B5
D6
D5

Slot C

T+/R+

• Wire T-/R- to the A terminal of

the EIA-485 port.

• Wire T+/R+ to the B terminal of

the EIA-485 port.

• Wire common to the common

terminal of the EIA-485 port.

• Do not route network wires

with power wires. Connect net-

work wires in daisy-chain fash-

ion when connecting multiple

devices in a network.

• A termination resistor may be

required. Place a 120 Ω resistor

across T+/R+ and T-/R- of last

controller on network.

• Only one protocol per port is

available at a time: either Mod-

bus RTU or Standard Bus.

• Do not connect more than 16

controllers on a Standard Bus

network.

• Do not connect more than 247

controllers on a Modbus RTU

network.

• maximum network length:

1,200 meters (4,000 feet)

• 1/8th unit load on EIA-485 bus.
ST _ _ - _ _ M _ - _ _ _ _ (Modbus

RTU or EIA-485)

Modbus-IDA

Terminal

EIA/TIA-485

Name

Watlow Termi-

nal Label

Function

DO

A

CA or CD

T-/R-

D1

B

CB or CE

T+/R+

common

common

CC or CF

common