Global menu – Watlow EZ-ZONE ST User Manual
Page 54
Watlow EZ-ZONE
®
ST
•
52
•
Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to use
for temperature.
[```F]
°F (30)
[```C]
°C (15)
°F
Instance 1
Map 1 Map 2
- - - - 1698
- - - -
110
3005
- - - - uint
RWES
[AC;LF]
[AC.LF]
Global
AC Line Frequency
Set the frequency to the
applied ac line power
source.
[``50]
50 Hz (3)
[``60]
60 Hz (4)
60 Hz
Instance 1
Map 1 Map 2
129
946
0x65 (101)
1
0x22 (34)
- - - -
1034 Inst. 1
886
uint
RWES
[P;typ]
[P.tyP]
Global
Profile StartType
Set the profile startup to
be based on a set point or
a process value.
[StPt]
Set Point (85)
[`Pro]
Process (75)
Set Point
Instance 1
Map 1 Map 2
302
3814
0x7A
(122)
1
8
- - - -
22008 Inst. 1
2914
uint
RWE
[`GSE]
[ gSE]
Global
Guaranteed Soak En-
able
Enables the guaranteed
soak deviation function in
profiles.
[`oFF]
Off (62)
[``on]
On (63)
Off
Instance 1
Map 1 Map 2
299
3810
0x7A
(122)
1
6
- - - -
22006 Inst. 1
2910
uint
RWE
[GSd1]
[gSd1]
Global
Guaranteed Soak De-
viation 1
Set the value of the de-
viation band that will be
used in all profile step
types. The process value
must enter the deviation
band before the step can
proceed.
0.0 to 9,999.000°F or units
0.0 to 5,555.000°C
10.0°F or
units
6.0°C
Instance 1
Map 1 Map 2
300
3812
0x7A
(122)
1
7
- - - -
22007 Inst. 1
2912
float
RWE
No Dis-
play
Global
Ramping Type
Defines whether profiles
will use time or rate
Rate (81)
Time (143)
Time
Instance 1
Map 1 Map 2
- - - - 3874
0x7A
(122)
1
0x26 (38)
- - - -
22038 Inst. 1
- - - -
uint
RWE
[d;prs]
[d.PrS]
Global
Display Pairs
Defines the number of
Display Pairs.
1 to 10
2
Instance 1
Map 1 Map 2
- - - - 1744
- - - -
- - - -
3028
- - - - uint
RWES
[USr;S]
[USr.S]
Global
User Settings Save
Save all of this control-
ler's settings to the se-
lected set.
[SEt1]
User Set 1 (101)
[SEt2]
User Set 2 (102)
[none]
None (61)
None
Instance 1
Map 1 Map 2
17
26
0x(101)
1
0xE (14)
118
1014 Inst. 1
26
uint
RWE
[USr;r]
[USr.r]
Global
User Restore Settings
Replace all of this con-
troller's settings with
another set.
[FCty]
Factory (31)
[none]
None (61)
[SEt1]
User Set 1 (101)
[SEt2]
User Set 2 (102)
None
Instance 1
Map 1 Map 2
16
24
0x65
(101)
1
0xD (13)
117
1013 Inst. 1
24
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EE-
PROM
S:
User
Set