Chapter 5: profiling page, Profiling parameters, How to start a profile – Watlow EZ-ZONE ST User Manual
Page 56

Watlow EZ-ZONE
®
ST
•
54
•
Chapter 5 Profile Page
Chapter 5: Profiling Page
5
The Profiling Page allows you to enter your ramp
and soak profile information.
To go to the Profiling Page from the Home Page,
press the Advance Key
‰
for three seconds, until
[ProF]
appears in the lower display and the profile
number appears in the upper display. Press the Up
¿
or Down ¯ key to change to another profile.
• Press the Advance Key
‰
to move to the selected
profile's first step.
• Press the Up ¿ or Down ¯ keys to move
through the steps.
• Press the Advance Key
‰
to move through the
selected step's settings.
• Press the Up ¿ or Down ¯ keys to change the
step's settings.
• Press the Infinity Key ˆ at any time to return
to the step number prompt.
• Press the Infinity Key ˆ again to return to the
profile number prompt.
• From any point press and hold the Infinity Key
ˆ
for two seconds to return to the Home Page.
Note:
Changes made to profile parameters in the Profiling Pages will be
saved and will also have an immediate impact on the running pro
file .
Some parameters in the Profile Status Menu can be
changed for the currently running profile, but should only
be changed by knowledgeable personnel and with caution .
Changing parameters via the Profile Status Menu will not
change the stored profile but will have an immediate im-
pact on the profile that is running .
How to Start a Profile
After defining the profile follow the steps below to
run the profile:
1. From the Home Page push the Advance Key
‰
repeatedly until Profile Start [P;St1] appears in
the lower display.
2. Use the Up ¿ or Down ¯ key to choose the file
or step number within a profile where you want
the profile to begin running.
3. Press the Advance Key
‰
. This takes you to Pro-
file Action [P;AC1], where you can select the ap-
propriate action.
• [none] No action
• [ProF] Begin execution from first step of the
specified profile number, whether it exists or
not.
• [PAUS] Pause the currently running profile.
• [rESU] Resume running the profile from the
previously paused step.
• [`End] End the profile.
• [StEP] Begin running the profile from the spec-
ified step number.
Note:
Avoid continuous writes within loops . Excessive writes to EEPROM
will cause premature EEPROM failure . The EEPROM is rated for
1,000,000 writes . Navigate to Setup Page under the Com menu
and set prompt Non-volatile Save
[`nU;S] to No .
Profiling Parameters
[prof]
Profile
[``p1]
to [``p4]
[``p1]
Step 1 (to 10)
[``p2] Step 11 (to 20)
[``p3] Step 21 (to 30)
[``p4] Step 31 (to 40)
[S;typ]
Step Type
[t;SP1]
Target Set Point Loop 1
[hoUr]
Hours
[Min]
Minutes
[`SEC]
Seconds
[RATE]
Rate
[W;P1]
Wait For Process 1
[WE;1]
Wait Event 1
[WE;2]
Wait Event 2
[``JS]
Jump Step
[``JC]
Jump Count
[`EnD] End Type
[Ent1] Event 1
[Ent2] Event 2
Note:
This page appears only if 10
th
digit of part number is P