Manual I/O Test

Press Yes at this prompt to see menus which can help you test the digital
inputs, digital outputs and the CAS' keypad.

Digital Input Testing

This is a read-only menu that shows the logic state of the 8 digital inputs
as H (High- the input is at 5 volts or is not connected) or L (Low- the
input is at zero volts). Inputs 1 to 8 are displayed from left to right.
Since inputs are pulled High when they are not connected, test an input
by shorting it to controller common and making sure this menu shows
the correct state for that input.

Digital Output Selection

This menu lets you select one of the digital alarm outputs to test in the
next menu.

CHANNEL PROCESS UNITS

CHANNEL NAME ALARM STATUS

MANUAL I/O
TEST ?

CHANNEL PROCESS UNITS

CHANNEL NAME ALARM STATUS

DIGITAL INPUTS
HHLLHHHH

CHANNEL PROCESS UNITS

CHANNEL NAME ALARM STATUS

TEST DIGITAL
OUTPUT ? 34