Specifications, Analog inputs – Watlow CAS User Manual
Page 13
Introduction
CAS User’s Guide 3
Specifications
This section contains specifications for inputs, serial interface, system
power requirements, environmental specifications, and physical
dimensions.
Analog Inputs
Number of Analog Inputs: 16 single-ended/ common ground, plus one
pulse input.
Input Switching: solid state MUX switching.
Input Sampling Rate: 1.5x/second (667 ms) at 60 Hz; 1.25x/second
(300 ms) at 50 Hz.
Analog Over Voltage Protection: ±20 V referenced to digital ground.
A/D Converter: Integrates voltage to frequency.
Input Range: -10 to +60 mV. Other ranges are available with scaling
resistors.
Resolution: 0.006%, greater than 14 bits. (This is the internal
measurement resolution, not the display resolution.)
Calibration: Automatic zero and full scale.
T/C Break Detection: Pulse type for upscale break detection.
Milliamp inputs: 0-20 mA (3 ohms resistance) or 0-10 mA (6 ohms
resistance), with scaling resistors.
Thermocouple Ranges and Accuracy
T/C Type
Range in ºF
Range in ºC
*Accuracy:
25ºC
Ambient
*Accuracy:
0 - 50º C Full
Temp. Range
ºC
ºF
ºC
ºF
J T/C
-350 to 1400
-212 to 750
±0.5
±0.9
±1.1
±2.0
K T/C
-450 to 2500
-268 to 1371
±0.6
±1.2
±1.35
±2.7
T T/C
-450 to 750
-268 to 399
±1.3
±2.4
±2.9
±5.4
S T/C
0 to 3200
-18 to 1760
±2.5
±4.5
±5.6
±10.1
R T/C
0 to 3210
-18 to 1766
±2.5
±4.5
±5.6
±10.1
B T/C
150 to 3200
+66 to 1760
±6.6
±12.0
±14.9
±27.0
N T/C
-450 to 2370
-268 to 1299
±1.0
±1.8
±2.25
±4.1
PL-II T/C
+50 to 2012
+10 to 1100
±0.6
±1.0
±1.2
±2.2
* True for 10% to 100% of span.