Input Units

The Input Units menu lets you choose a three-character description of
the channel's engineering units.

Thermocouples can only be ºF or ºC.

If you have selected a linear or pulse input type, you can choose any

available character for each character position. For example, you can
use GPM or PSI or % for a linear input's units.

The table below shows the character set for input units.

Input Reading Offset

This menu lets you set an input reading offset function to make up for
the input signal's inaccuracy at any given point. For example, at
temperatures below 400

°

F, a type J thermocouple may be inaccurate

("offset") by several degrees F. Use an independent thermocouple or
your own calibration equipment to find the offset for your equipment.
To correct for offset errors, change the factory default setting to a
positive or negative value for the channel you are editing. (A positive
value increases the reading and a negative value decreases it.)

Selectable values: -300 to 300 for thermocouples

NOTE

If the input type is set to Linear, Pulse, or Skip, you will not see this
menu.

Input

Character Sets for Units

Thermocouple

ºF or ºC

Linear & Pulse

0-9, A-Z, %, /,º, space

CHANNEL PROCESS UNITS

CHANNEL NAME ALARM STATUS

02 INPUT
UNITS ? °F

CHANNEL PROCESS UNITS

CHANNEL NAME ALARM STATUS

01 INPUT READING
OFFSET ? 0° F