62 CAS User’s Guide

Setup

Low Deviation Alarm Output Number

This menu is used to assign a digital output that activates when the
channel is in low deviation alarm.

Selectable values: 1 to 34, None

NOTE

All digital outputs are OR'd together (combined). Therefore you
can assign more than one alarm to the same output number, and that
output will be On if any of those alarms is On.

Low Process Alarm Setpoint

This menu is used to set a low process alarm setpoint. (The low process
alarm activates when the process variable goes below the low process
alarm setpoint. It deactivates when the process variable goes above the
low process alarm setpoint plus the deadband.)

Selectable values: Any value within the input sensor's range

Low Process Alarm Type

This menu lets you turn off the low process alarm or set it to the alarm
function.

Selectable values: Off, Latched, Unlatched

CHANNEL PROCESS UNITS

CHANNEL NAME ALARM STATUS

01 LO DEV ALARM
OUTPUT ? NONE

CHANNEL PROCESS UNITS

CHANNEL NAME ALARM STATUS

01 LO PROC ALARM
SETPT ? 0

CHANNEL PROCESS UNITS

CHANNEL NAME ALARM STATUS

01 LO PROC ALARM
TYPE ? OFF