FP3000 Series User Manual
5-8
5.2
Wiring
5.2.1
Connecting the Power Cord
FP3500-T11/FP3600-T11/FP3650-T41 (Type AC)
Power Cord Specifications
To avoid an electric shock, when connecting the FP’s power cord terminals to the power
terminal block, confirm that the FP’s power supply is completely turned OFF, via a breaker,
or similar unit.
To avoid the dangers of fire, electric hazards and equipment damage, be sure to use only
the specified voltage when operating the FP.
Since there is no power switch on the FP unit, be sure to attach a breaker-type switch to its
power cord.
• To prevent the Ring Terminals
*1
from causing a short when the terminal block
attachment screws are loosened, be sure to use sleeve-type Ring Terminals.
• When the FG terminal is connected, be sure the wire is grounded. Not grounding
the FP unit will result in excessive noise. Use your country’s applicable standard
for grounding.
• The SG and FG terminals are connected internally in the FP unit.
• When connecting the SG line to another device, be sure that the design of the
system/connection does not produce a shorting loop.
*1
Recommended Ring Terminal: Equivalent to V2-MS3 (made by JST)
AC Power Cord
Grounding Wire
Power Cord
Double-Insulation Wire
1.25 mm
2
to 2.0 mm
2
(16 to 14 AWG)
1.25 mm
2
to 2.0 mm
2
(16 to 14 AWG)
Recommended
Ring Terminal
*1
*1
In order to prevent a short circuit caused by loose screws, make sure to use a crimp-
type terminal with insulating sleeve.
V2-MS3 compatible
(J.S.T. Mfg. Co.,Ltd).
V2-P4 compatible
(J.S.T. Mfg. Co.,Ltd).
SEE
5.2.3 Connecting the Power Supply (page5-15)
Over ø3.2 mm[0.13 in.]
Under 6.0 mm
[0.24 in.]
Over ø4.3 mm[0.17 in.]
Under 7.0 mm
[0.28 in.]