Be aware of the following items when building the LT into an end-use product:
• The LT unit’s rear face is not approved as an enclosure. When building the LT unit into an end-use product, be sure to
use an enclosure that satisfies standards as the end-use product’s overall enclosure.
• The LT unit must be used indoors only.
• Install and operate the LT with its front panel facing outwards.
• If the LT is mounted so as to cool itself naturally, be sure to install it in a vertical panel. Also, it’s recommended that
the LT should be mounted at least 100 mm away from any other adjacent structures or machine parts. The temperature
must be checked on the final product in which the LT is installed.
• For use on a flat surface of a Type 4X (Indoor Use Only) and/or Type 13 Enclosure.
*1 > (1) Suitable for use in Class I, Division 2, Groups A, B, C, and D Hazardous Locations, or Non-Hazardous Locations. (2) WARNING: Explosion hazard-substitution of any components may impair compliance to Class I, Division 2. (3) WARNING: Explosion hazard-when in hazardous locations, turn the power OFF before replacing or wiring modules. (4) WARNING: Explosion hazard-do not disconnect equipment unless power has been switched off or the area is known to be Non-Hazardous. (5) In the case of use in Hazardous Locations, be sure to check that the externally connected unit and each interface have been fixed with screws and locked. In Hazardous Locations, it’s impossible to insert or pull the cable from the applicable port. Be sure to check that the location is Non-Hazardous before inserting or pulling it. The safety certificate can be downloaded from Pro-face Home Page. *1The compliant Rev. with Hazardous Locations are as follows. SEE
Home Page URL
http://www.pro-face.com/
LT-3300T : all Rev.
LT-3300S, LT-3300L, LT-3301L : Rev.1