REV 1 CT-8000 S3 USER’S MANUAL
62
3.3.4. Performing an On-Line Timing Test on Live Contacts
The optional "On-line" timing mode (part no. 9103-OT) can be used to capture the breaker's
trip or close time, the trip/close coil current “fingerprint”, and the battery supply voltage while
the breaker is still in service. The On-line timing mode requires an external trigger on the coil
being tested.
Follow the steps below to perform an on-line timing test (an OPEN test example is shown
below):
a. Make the cable connections per Figure 8 and then start from the "START-UP" menu:
Press the
[1]
key (RUN TEST).
b. The following screen will be displayed:
Press the
[2]
key (TIME LIVE CONTACTS).
c. The following screen will be displayed:
Press the
[1]
key (OPEN).
TIMING MODE:
1.
OPEN 2. CLOSE
3. O-C 4. C-O
1.
TIME DRY CONTACTS
2.
TIME LIVE CONTACTS
3.
STATIC RES TEST
4.
DYNAMIC RES TEST
1.
RUN TEST 10/08/13
2.
GET RESULTS 10:10:10
3.
SAVE/RESTORE
4.
SETUP
5.
DIAGNOSTICS