CT-8000 S3 USER’S MANUAL

REV 1

53

Select the resistance value by pressing the corresponding key (

[1]

,

[2]

, or

[3]

).

Continue to step d.

d. The following screen will be displayed:

Press the

[1]

key (WINDOW = 1 SEC).

NOTE

The 1-second timing window is used for breaker timing. The 10 and 20-
second timing windows are used for long timing events such as for timing
circuit-switchers.

e. The following screen will be displayed:

Press the

[1]

key (INTERNAL TRIGGER).

f. The following screen will be displayed:

Press the

[1]

key (OPEN).

TIMING MODE:

1.

OPEN 2. CLOSE

3. O-C 4. C-O
5. O-C-O

TRIGGER MODE:

1.

INTERNAL TRIGGER

2.

EXTERNAL TRIGGER


TIMING WINDOW:

1.

WINDOW = 1 sec

2.

WINDOW = 10 SEC

3.

WINDOW = 20 SEC


resistor value:

1.

LESS THAN 1000 OHMS

2.

1000 to 2000 OHMS

3.

MORE THAN 2000 OHMS