TABLE 24
ANALOG INPUT "2" ELECTRICAL RATINGS
Parameter Specification
Factory
setting
Voltage Range (Volts DC)
0 – ±2.5 thru 0 – ±25
0 – 5
MAX2 Scaling Trimpot Range (Volts DC)
0 – 24
5
Current Range (mA DC)
0 – 20*
–
Input Impedance for Current Mode (Ω) 270
–
PWM (kHz, Duty Cycle)
0.15 – 1, 0 – 100
–
*If using 4 – 20 mA DC signal input, the offset setting in Function No. 9.07 must be
increased from "0%" (factory setting) to "20%". Set Jumper J1 to the "CUR" position.
TABLE 25
ANALOG INPUT "2" SIGNAL CURRENT FOLLOWING PROGRAMMING
Function No.
Code/Range
2.00: Frequency Control 0003:
Analog Signal 2
9.05: Analog Input 2 Gain 0
–
500:
Set to the Desired Gain
7.04: Multi-Function Input Terminal 5
0010: N.O. Start*
9.06: Analog Input 2 Slope
0000: Positive
0001: Negative
9.07: Analog Input 2 Offset 0
–
100:
Set to the Desired Offset
9.08: Analog Input 2 Type
0000: Analog Voltage or Current
9.09: Analog Input 2 Response Time (mSec) 2 – 100: Set to the Desired Time
*Factory setting.
FIGURE 33
ANALOG INPUT "2" SIGNAL CURRENT FOLLOWING CONNECTIONS
MAX2 Trimpot
and Jumper J1
+
A9. ANALOG SIGNAL OUTPUT
Two analog signal outputs are provided, which will linearly follow the parameter programmed in Analog output
1 Mode (Function No. 8.06) and Analog Output 2 Mode (Function No. 8.08). They can be used to monitor
Motor Frequency, Set Frequency, Motor Voltage, Bus Voltage, and Motor Current. See Figure 34, on page
44, for Analog Output 1 and 2 Gain settings (factory set to 100%). See Table 26, for Analog Outputs 1 and 2
electrical ratings. See Table 27, on page 44, for drive programming. See Figure 35, on page 44, for
connections.
Analog Output 1 provides a voltage signal output. Analog Output 2 provides a voltage or current signal output.
TABLE 26
ANALOG OUTPUTS "1" AND "2" ELECTRICAL RATINGS
Parameter Specification
Factory
setting
Analog Outputs 1 and 2 Voltage Range (Volts DC)
0 – 5
0 – 5
Analog Output 2 Current Range (mA DC)
0 – 20, 4 – 20
–
Analog Output 2 Impedance for Current Mode (Ω)
150 –