USING IODA MULTI-FUNCTION INPUT TERMINALS FOR REMOTE OPERATIONS
A1. PRESET FREQUENCIES
The drive is factory programmed for 7 Preset Frequencies, which can be selected using remote switches or
contacts connected to Multi-Function Input Terminals "1" – "3". See Table 13, for drive programming. See
Figure 22, for connections. See Table 14, on page 34, for the Multi-Function Input Terminals to select for the
preset frequencies.
The 7 Preset Frequencies are obtained using a combination of Multi-Function Input Terminals 1, 2, 1+2, 3,
1+3, 2+3, 1+2+3. The Preset Frequencies can be changed from their factory settings by reprogramming
Function Nos. 7.07 – 7.13.
8
th
Preset Frequency: If none of the Multi-Function Input Terminals are activated, the drive will operate at the
Stored Set Frequency (Function No. 3.00) of 5.00 Hz. If the 8
th
Preset Frequency is not required, set Function
No. 3.00 to 00.00 Hz.
Note: For Preset Frequency Operation only, the drive does not have to be reprogrammed for External
Contacts Operation. Multi-Function Input Terminals "1" – "3" are factory set to codes "0000", "0001", and
"0002", which automatically sets the drive for Preset Frequency Operation.
TABLE 13
PRESET FREQUENCY SELECTION WITH 2-WIRE START/STOP PROGRAMMING
Function No.
Code/Range
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
3.00: Stored Set Frequency
00.00 Hz
7.00: Multi-Function Input Terminal 1
0000: Preset Frequency Operation*
7.01: Multi-Function Input Terminal 2
0001: Preset Frequency Operation*
7.02: Multi-Function Input Terminal 3
0002: Preset Frequency Operation*
7.04: Multi-Function Input Terminal 5
0010: N.O. Start*
*Factory setting.
FIGURE 22
PRESET FREQUENCY SELECTION
WITH 2-WIRE START/STOP CONNECTIONS
Note: Use Function Nos. 7.07 – 7.13 to program the desired Preset
Frequencies.