KB Electronics KBMK-24DF User Manual
Page 26
26
FUNCTION GROUP 6 – Drive Status and Reset
Function
No. Description
Code
Factory
Setting
6.00 * Software Version
──
──
6.01 * Drive Horsepower
──
──
6.02 * Fault Log 1
──
──
6.03 * Fault Log 2
──
──
6.04 * Fault Log 3
──
──
6.05 ** Reset Drive to Factory Setting
1110: 50 Hz Operation
1111: 60 Hz Operation
0000
*Read only.
**Functions which can only be changed while the drive is in the Stop Mode.
FUNCTION GOUP 7 – Multi-Function Input Terminals (IODA Option Board Required)
Function
No. Description
Range/Code
Factory
Setting
7.00 *
Multi-Function
Input Terminal 1
(1)
0000
7.01 *
Multi-Function
Input Terminal 2
(1)
0001
7.02 *
Multi-Function
Input Terminal 3
(1)
0002
7.03 *
Multi-Function
Input Terminal 4
(1)
0009
7.04 *
Multi-Function
Input Terminal 5
(1)
0010
7.05 *
Multi-Function
Input Terminal 6
(1)
0003
7.06 *
Multi-Function
Input Terminal 7
(1)
0000: Preset Frequency Operation
(2)
0001: Preset Frequency Operation
(2)
0002: Preset Frequency Operation
(2)
0003: Up Frequency Command
(See Function No. 7.14)
(3)
0004: Down Frequency Command
(See Function No. 7.14)
(3)
0005: Accel/Decel 2 (See Function No. 7.16)
0006: Forward/Stop Command
(4)
0007: Reverse/Stop Command
(4)
0008: External Fault (N.O. Contact)
0009: Reset
0010: N.O. Start (2-Wire or 3-Wire Start/Stop)
(4)
0011: N.C. Stop (3-Wire Start/Stop)
(4)
0012: External Fault (N.C. Contact)
0004
7.07
Preset Frequency 1 (Hz)
0.00 – 240.0
5.00
7.08
Preset Frequency 2 (Hz)
0.00 – 240.0
10.00
7.09
Preset Frequency 3 (Hz)
0.00 – 240.0
20.00
7.10
Preset Frequency 4 (Hz)
0.00 – 240.0
25.00
7.11
Preset Frequency 5 (Hz)
0.00 – 240.0
30.00
7.12
Preset Frequency 6 (Hz)
0.00 – 240.0
35.00
7.13
Preset Frequency 7 (Hz)
0.00 – 240.0
40.00
7.14
Up/Down Frequency Control Mode
0000: Free-Running
(5)
0001: Incremental Change (See Function No. 7.15)
0000
7.15
Increment of Up/Down Frequency (Hz) 0.01 – 30.00
1.00
7.16
Accel/Decel 2 Time (Seconds)
0.3 – 180.0
1.5
Note: (1) Each of the 7 Multi-Function Inputs can be programmed for any of the respective function codes ("0000" –
"0011"). (2) Preset Frequencies 1 – 7 are obtained by selecting a specific combination of 3 Multi-Function Input
Terminals. The specific frequencies are programmed in Function Nos. 7.07 – 7.13. See Appendix A1, on page 33.
(3) For Up/Down Frequency Commands (codes "0003" and "0004"), Frequency Control (Function No. 2.00) must be
set to Up/Down Using MFITs (code "0005"). (4) For Forward/Reverse Stop Commands (codes "0006" and "0007")
and N.O. Start / N.C. Stop (codes "0010" and "0011"), Run/Stop-Forward/Reverse Control (Function No. 1.00) must
be set to External Contacts (code "0001"). (5) The rate of change of the "UP" Control for frequency setting, using
external contacts, is proportional to the Accel Time setting (Function No. 3.03). The rate of change of the "DOWN"
Control for frequency setting, using external contacts, is proportional to the Decel Time Setting (Function No. 3.04).
*Functions which can only be changed while the drive is in the Stop Mode.